CalcWorldHub
Free online calculator · no signup

Constant-power supercapacitor hold-up calculator

Size a supercapacitor bank discharge interval for a regulated load whose current increases as voltage falls.

4,000 tools
Constant-power supercapacitor hold-up calculator — Effective series-bank capacitance (F), Initial bank voltage (V), Converter cutoff voltage (V) and calculation method
Constant-power supercapacitor hold-up calculator: inputs and calculation method.

How to use this calculator

Size a supercapacitor bank discharge interval for a regulated load whose current increases as voltage falls.

  1. Enter Effective series-bank capacitance (F), Initial bank voltage (V), Converter cutoff voltage (V), Regulated load power (W), then complete the remaining labeled fields. Match the units shown beside each field and review the result together with the assumptions below.
  2. Read the worked example below to check the expected input format and result.
  3. Compare another scenario by changing one input at a time. Use Reset to return to the starting values.
Calculation guide

Constant-power supercapacitor hold-up explained

Hold-up duration18.144s
Hold-up duration: 18.144 s in the worked scenario.

How the calculation works

t_H=ηC(V_H²−V_L²)/(2P_OUT); E_USE=C(V_H²−V_L²)/2.

Integrate the capacitor energy removed between two voltage limits. Constant output power with constant efficiency fixes input power, not capacitor current.

Set up the calculation

C — Effective series-bank capacitance (F)
Equivalent bank capacitance after series connection.
Vhi — Initial bank voltage (V)
Starting bank terminal voltage before ideal discharge.
Vlo — Converter cutoff voltage (V)
Minimum usable capacitor voltage.
P — Regulated load power (W)
Constant downstream output power.
eta — Converter efficiency
Constant output-to-input power ratio.

Limits of this model

Ignores ESR drop, leakage, capacitance tolerance and converter minimum/maximum current constraints.

Check this example

Effective series-bank capacitance (F) = 10; Initial bank voltage (V) = 5.4; Converter cutoff voltage (V) = 3; Regulated load power (W) = 5; Converter efficiency = 0.9.

  • Hold-up duration: 18.144 s
  • Usable capacitor energy: 100.8 J
  • Initial input current: 1.028807 A

A 10 F bank discharging from 5.4 V to 3 V provides 100.8 J; at 90% efficiency a 5 W load runs about 18.144 seconds.

Reading the outputs

Initial input current is only the starting value; it rises toward cutoff. Energy excludes the unusable energy remaining below Vlo.

Frequently asked questions

Why is C times delta V divided by current unsuitable?

That expression assumes constant current; a regulated constant-power load draws increasing current.

Do series capacitors keep the individual capacitance?

No; enter the equivalent bank capacitance and bank voltage.

Can zero cutoff be used?

The ideal energy formula permits it, but real converters cannot deliver finite constant power at zero voltage.

How do I use the Constant-power supercapacitor hold-up calculator?

Enter Effective series-bank capacitance (F), Initial bank voltage (V), Converter cutoff voltage (V), Regulated load power (W), then complete the remaining labeled fields. Match the units shown beside each field and review the result together with the assumptions below.

What is a worked example of Constant-power supercapacitor hold-up?

Effective series-bank capacitance (F) = 10; Initial bank voltage (V) = 5.4; Converter cutoff voltage (V) = 3; Regulated load power (W) = 5; Converter efficiency = 0.9. Hold-up duration: 18.144 s Usable capacitor energy: 100.8 J Initial input current: 1.028807 A A 10 F bank discharging from 5.4 V to 3 V provides 100.8 J; at 90% efficiency a 5 W load runs about 18.144 seconds.