How to use this calculator
Predict exchanger duty and outlet temperatures from conductance and capacity rates instead of assuming measured heat transfer.
- Enter Overall conductance UA (W/K), Hot-stream heat-capacity rate (W/K), Cold-stream heat-capacity rate (W/K), Hot inlet temperature (°C), then complete the remaining labeled fields. Match the units shown beside each field and review the result together with the assumptions below.
- Read the worked example below to check the expected input format and result.
- Compare another scenario by changing one input at a time. Use Reset to return to the starting values.
Counterflow parallel flow NTU exchanger model explained
Use Overall conductance UA (W/K) with Hot-stream heat-capacity rate (W/K) to reproduce the sample calculation, then review the stated limits before carrying the result into another scenario.
How the calculation works
Effectiveness from NTU=UA/Cmin and Cr=Cmin/Cmax
Identify the smaller capacity rate and form NTU=UA/Cmin and Cr=Cmin/Cmax. Use the selected ideal arrangement to obtain effectiveness, multiply by Cmin times inlet temperature difference, and subtract/add that duty from the hot/cold stream energy balances.
Set up the calculation
u— Overall conductance UA (W/K)- Overall conductance UA (W/K).
c1— Hot-stream heat-capacity rate (W/K)- Hot-stream heat-capacity rate (W/K).
c2— Cold-stream heat-capacity rate (W/K)- Cold-stream heat-capacity rate (W/K).
th— Hot inlet temperature (°C)- Hot inlet temperature (°C).
tc— Cold inlet temperature (°C)- Cold inlet temperature (°C).
m— Flow arrangement- Flow arrangement. Choose counterflow, parallel.
Limits of this model
Constant properties, no external heat loss, and ideal pure counterflow or parallel flow. No phase change or shell-pass correction is included.
Check this example
Overall conductance UA (W/K) = 1000; Hot-stream heat-capacity rate (W/K) = 500; Cold-stream heat-capacity rate (W/K) = 800; Hot inlet temperature (°C) = 80; Cold inlet temperature (°C) = 20; Flow arrangement = counterflow.
- Predicted exchanger effectiveness: 0.74865952
- Heat transfer rate: 22459.785607 W
- Hot outlet temperature: 35.080429 °C
- Cold outlet temperature: 48.074732 °C
Displayed values are rounded only after calculation.
Frequently asked questions
How does this differ from Q/Qmax effectiveness?
It predicts effectiveness from UA and stream capacity rates.
What if capacity rates are equal?
Counterflow uses the NTU/(1+NTU) limit.
Can UA be zero?
Yes, no heat is transferred.
How do I use the Counterflow parallel flow NTU exchanger model calculator?
Enter Overall conductance UA (W/K), Hot-stream heat-capacity rate (W/K), Cold-stream heat-capacity rate (W/K), Hot inlet temperature (°C), then complete the remaining labeled fields. Match the units shown beside each field and review the result together with the assumptions below.
What is a worked example of Counterflow parallel flow NTU exchanger model?
Overall conductance UA (W/K) = 1000; Hot-stream heat-capacity rate (W/K) = 500; Cold-stream heat-capacity rate (W/K) = 800; Hot inlet temperature (°C) = 80; Cold inlet temperature (°C) = 20; Flow arrangement = counterflow. Predicted exchanger effectiveness: 0.74865952 Heat transfer rate: 22459.785607 W Hot outlet temperature: 35.080429 °C Cold outlet temperature: 48.074732 °C Displayed values are rounded only after calculation.