How to use this calculator
Calculate the share of data-center energy beneficially reused elsewhere.
- Enter Energy reused outside the data center (kWh), Total data-center energy consumed (kWh). Match the units shown beside each field and review the result together with the assumptions below.
- Read the worked example below to check the expected input format and result.
- Compare another scenario by changing one input at a time. Use Reset to return to the starting values.
How this calculation works
Energy Reuse Factor (ERF) measures the energy from a data center that is beneficially reused outside its boundary relative to the total data-center energy consumed over the same period.
Inputs and units
reusedEnergyKwh— Energy reused outside the data center (kWh)- Energy recovered for beneficial use beyond the data-center boundary.
totalEnergyKwh— Total data-center energy consumed (kWh)- Total energy consumed within the data-center boundary for the same period.
Formula
ERF = energy reused outside the data center ÷ total data-center energy consumed.
Method
Enter reused energy and total energy consumption for the same reporting period and energy boundary. Keep both quantities in the same unit.
Worked example
Reusing 250,000 kWh from a total data-center consumption of 1,000,000 kWh gives an ERF of 0.2500, or 25.00%.
Assumptions and limits
ERF measures the share of total energy reused, not whether the receiving use is efficient or beneficial in every context. Reuse outside the chosen boundary must be documented.
Frequently asked questions
Where must reused energy go?
Count energy that is beneficially used outside the defined data-center boundary.
What does the result mean?
The ratio shows the reused share of total data-center energy consumed.
What should I compare it with?
Compare using the same data-center boundary and period; count beneficial energy reused outside that boundary over total center energy consumed.
How do I use the Data Center Energy Reuse Factor (ERF) Calculator?
Enter Energy reused outside the data center (kWh), Total data-center energy consumed (kWh). Match the units shown beside each field and review the result together with the assumptions below.
What is a worked example of Data Center Energy Reuse Factor (ERF)?
Reusing 250,000 kWh from a total data-center consumption of 1,000,000 kWh gives an ERF of 0.2500, or 25.00%.