How to use this calculator
Calculate site water use per unit of IT equipment energy.
- Enter Site water used (L), IT equipment energy (kWh). Match the units shown beside each field and review the result together with the assumptions below.
- Read the worked example below to check the expected input format and result.
- Compare another scenario by changing one input at a time. Use Reset to return to the starting values.
How this calculation works
Water usage effectiveness (WUEsite) is a data-center KPI that relates water consumed on site to energy used by IT equipment over the same reporting period.
Inputs and units
siteWaterLiters— Site water used (L)- Water consumed within the data-center site boundary during the reporting period.
itEnergyKwh— IT equipment energy (kWh)- Energy consumed by IT equipment over the same period.
Formula
WUEsite = annual site water usage (L) ÷ IT equipment energy (kWh).
Method
Use site water inside the data-center boundary and IT equipment energy from the same period. This tool reports the direct site-water ratio, not upstream water used to generate electricity.
Worked example
One hundred million liters of site water divided by 1,000,000 kWh of IT energy gives a WUEsite of 100 L/kWh IT.
Assumptions and limits
WUE depends on climate, cooling design, water source, and reporting boundary. It is not a measure of total data-center energy efficiency.
Frequently asked questions
Does this include water used to generate electricity?
No. This is direct site water use divided by IT equipment energy; upstream water is outside this boundary.
What does the result mean?
Lower direct WUEsite means less site water used per unit of IT energy, within the stated boundary.
What should I compare it with?
Compare the same site-water boundary and IT-energy period; upstream water used to generate electricity is excluded from this site metric.
How do I use the Data Center Water Usage Effectiveness (WUE) Calculator?
Enter Site water used (L), IT equipment energy (kWh). Match the units shown beside each field and review the result together with the assumptions below.
What is a worked example of Data Center Water Usage Effectiveness (WUE)?
One hundred million liters of site water divided by 1,000,000 kWh of IT energy gives a WUEsite of 100 L/kWh IT.
Reference: ISO 30134-9, Data centres — Water usage effectiveness (WUE). See our calculation methodology.