Three-phase reactive power calculator
Estimate reactive power in a balanced three-phase circuit from voltage, current, and power factor. Enter your values below to see the result and method.
inputs.
Related calculators
These tools cover nearby questions while keeping this page focused on its own calculation.
How to use this calculator
Estimate reactive power in a balanced three-phase circuit from voltage, current, and power factor.
- Enter Line voltage (V), Line current (A), Power factor. Match the units shown beside each field and review the result together with the assumptions below.
- Read the worked example below to check the expected input format and result.
- Compare another scenario by changing one input at a time. Use Reset to return to the starting values.
Define the component and operating point
This gives reactive-power magnitude for a balanced sinusoidal load from line voltage, line current, and power factor. It does not indicate leading or lagging sign. Estimate reactive power in a balanced three-phase circuit from voltage, current, and power factor.
Inputs and units
Use the units printed beside each field. These values are Line voltage (V), Line current (A), Power factor.
- Line voltage (V): Line voltage as defined for the physical or engineering situation.
- Line current (A): Line current as defined for the physical or engineering situation.
- Power factor: Enter power factor as a fraction from zero to one; this calculator does not encode leading versus lagging direction.
Design equation and example
Q = √3 Vₗ Iₗ sin(arccos PF)
A 400 V, 20 A load at PF 0.80 has about 8.31 kvar.
Intermediate values are kept unrounded; the displayed result is rounded for readability.
Applying the result in a system
This gives reactive-power magnitude for a balanced sinusoidal load from line voltage, line current, and power factor. It does not indicate leading or lagging sign.
Assumptions and limitations
Assumes balanced sinusoidal operation; power-factor sign and leading/lagging direction are omitted.
Frequently asked questions
Which measurements belong in the three-phase reactive power?
Enter Line voltage (V), Line current (A), Power factor. Verify that the values use the same operating condition and unit system.
What can make a real installation differ from this three-phase reactive power estimate?
Assumes balanced sinusoidal operation; power-factor sign and leading/lagging direction are omitted.
How do I use the Three-phase reactive power calculator?
Enter Line voltage (V), Line current (A), Power factor. Match the units shown beside each field and review the result together with the assumptions below.
What is a worked example of Three-phase reactive power?
Q = √3 Vₗ Iₗ sin(arccos PF) A 400 V, 20 A load at PF 0.80 has about 8.31 kvar. Intermediate values are kept unrounded; the displayed result is rounded for readability.
What does the Three-phase reactive power calculator calculate?
Estimate reactive power in a balanced three-phase circuit from voltage, current, and power factor.