Three-Phase Voltage Unbalance Calculator

Calculate NEMA voltage unbalance from three line-to-line RMS voltages on a three-phase supply.

4,000 tools
Three-Phase Voltage Unbalance Calculator — Line voltage V₁ (V RMS), Line voltage V₂ (V RMS), Line voltage V₃ (V RMS) and calculation method
Three-Phase Voltage Unbalance Calculator: inputs and calculation method.

How to use this calculator

Calculate NEMA voltage unbalance from three line-to-line RMS voltages on a three-phase supply.

  1. Enter Line voltage V₁ (V RMS), Line voltage V₂ (V RMS), Line voltage V₃ (V RMS). Match the units shown beside each field and review the result together with the assumptions below.
  2. Read the worked example below to check the expected input format and result.
  3. Compare another scenario by changing one input at a time. Use Reset to return to the starting values.
Electronics calculation

How this calculation works

The NEMA magnitude method compares the largest deviation from the average line voltage with that average.

Inputs and units

v1 — Line voltage V₁ (V RMS)
First measured line-to-line RMS voltage.
v2 — Line voltage V₂ (V RMS)
Second measured line-to-line RMS voltage.
v3 — Line voltage V₃ (V RMS)
Third measured line-to-line RMS voltage.

Formula

Displayed formula

V̄ = (V₁ + V₂ + V₃)/3; unbalance (%) = 100 · max|Vᵢ − V̄| / V̄.

Method

The calculator finds the arithmetic mean of the three measured line-to-line RMS magnitudes and divides the maximum absolute deviation by that mean. It reports the NEMA percent voltage-unbalance measure.

Worked example

For measured voltages of 462 V, 463 V, and 455 V, the average is 460 V, the maximum deviation is 5 V, and NEMA voltage unbalance is 1.087% (about 1.1%).

Assumptions and limits

Use three line-to-line RMS voltage magnitudes measured at the same three-phase terminals. This NEMA magnitude method is not the positive/negative-sequence component ratio; motor derating and allowable limits depend on the applicable equipment guidance.

Frequently asked questions

Which voltage readings should I enter?

Enter the three line-to-line RMS magnitudes measured on the same three-phase system and at the same operating condition.

Is this the symmetrical-components method?

No. It is the NEMA maximum-deviation-from-average magnitude method.

Does the result determine whether a motor is safe to operate?

No. Compare the measured condition with the motor manufacturer’s instructions and the applicable standard.

How do I use the Three-Phase Voltage Unbalance Calculator?

Enter Line voltage V₁ (V RMS), Line voltage V₂ (V RMS), Line voltage V₃ (V RMS). Match the units shown beside each field and review the result together with the assumptions below.

What is a worked example of Three-Phase Voltage Unbalance?

For measured voltages of 462 V, 463 V, and 455 V, the average is 460 V, the maximum deviation is 5 V, and NEMA voltage unbalance is 1.087% (about 1.1%).