How to use this calculator
Sum winding I²R losses using actual RMS currents and winding resistances.
- Enter Primary RMS current (A), Primary winding resistance (Ω), Secondary RMS current (A), Secondary winding resistance (Ω). Match the units shown beside each field and review the result together with the assumptions below.
- Read the worked example below to check the expected input format and result.
- Compare another scenario by changing one input at a time. Use Reset to return to the starting values.
Two winding transformer copper loss explained
Add the primary and secondary winding I²R losses using RMS current and resistance values from the same operating condition.
How the calculation works
a*a*b+c*c*d
AC resistance, temperature, and harmonics must be represented in the entered values; core loss is excluded.
Set up the calculation
a— Primary RMS current (A)- Primary RMS current (A).
b— Primary winding resistance (Ω)- Primary winding resistance (Ω).
c— Secondary RMS current (A)- Secondary RMS current (A).
d— Secondary winding resistance (Ω)- Secondary winding resistance (Ω).
Limits of this model
AC resistance, temperature, and harmonics must be represented in the entered values; core loss is excluded.
Check this example
Primary RMS current (A) = 1; Primary winding resistance (Ω) = 3; Secondary RMS current (A) = 8; Secondary winding resistance (Ω) = 0.08.
- Two winding transformer copper loss: 8.12 W
The example's winding losses add to 8.12 W. This is copper loss only; core loss and temperature-dependent resistance require separate data.
Method reference: OpenStax transformer loss example.
Frequently asked questions
Are core losses included?
No. The result is winding I²R loss; hysteresis and eddy-current core losses are separate.
Should resistance be measured hot?
Use the operating-temperature value.
Can RMS current include harmonics?
Yes, if the resistance basis remains appropriate.
How do I use the Two winding transformer copper loss calculator?
Enter Primary RMS current (A), Primary winding resistance (Ω), Secondary RMS current (A), Secondary winding resistance (Ω). Match the units shown beside each field and review the result together with the assumptions below.
What is a worked example of Two winding transformer copper loss?
Primary RMS current (A) = 1; Primary winding resistance (Ω) = 3; Secondary RMS current (A) = 8; Secondary winding resistance (Ω) = 0.08. Two winding transformer copper loss: 8.12 W The example's winding losses add to 8.12 W. This is copper loss only; core loss and temperature-dependent resistance require separate data. Method reference: OpenStax transformer loss example .
Read our calculation methodology.