Battery Capacity for Backup: Size Energy for a Target Runtime

A battery capacity for backup runtime estimate works backward from a target: how much nominal energy is needed to support a load for a stated number of hours? This calculator includes inverter efficiency and usable depth of discharge so that the battery nameplate capacity is larger than the energy delivered to the load. It is a planning model, not a product-selection approval.

Open calculator
A home backup battery is sized from a measured load and duration, then adjusted for inverter efficiency and usable discharge.

Share this article

Load energy is divided by inverter efficiency and usable discharge fraction to estimate nominal watt-hours.
Both losses enlarge the required nominal battery capacity.

Start with a defined load and duration

The inputs are average load in watts, backup time in hours, inverter efficiency in percent, and usable depth of discharge in percent. A load of 300 W for eight hours requests 2,400 Wh at the load before conversion and reserve limits are applied. Use average watts over the intended period, not the inverter’s maximum rating unless the load actually stays there.

Keep the two percentages distinct. Inverter efficiency describes the share of battery energy that reaches the AC load in this simplified model; usable depth of discharge describes how much of nominal battery capacity is planned for use. Enter 90 for 90%, not 0.90, because the input expects percentage points and converts them internally.

Derive nominal energy

The calculator divides load energy by both fractional factors: nominal Wh = load W × hours ÷ (efficiency/100) ÷ (usable DOD/100). If conversion efficiency is 90% and the planned usable window is 80%, their product is 0.72. Supplying 2,400 Wh to the load therefore requires 3,333.33333 Wh nominal in the arithmetic model.

Each factor changes the answer in the expected direction. A lower efficiency means more stored energy is needed for the same delivered energy; a smaller allowed discharge window also increases nameplate capacity. A zero or negative percentage cannot be used because it makes the denominator invalid, and values above 100% do not describe the percentages this calculator accepts.

Translate watt-hours into a battery size

The output is watt-hours, not amp-hours. To make a rough comparison with a battery listing in kWh, divide Wh by 1,000; 3,333.33333 Wh is about 3.333 kWh. To compare with Ah, nominal voltage is also required: Ah ≈ Wh ÷ V under a stated nominal-voltage convention. Do not pick a voltage merely to make a desired Ah number appear.

A 500 W load for four hours, using 92% inverter efficiency and a 75% usable window, gives 2,000 ÷ (0.92 × 0.75) = 2,898.55072 Wh. The calculator retains up to five decimal places in its displayed number. Practical equipment comes in discrete sizes, so use this computed requirement as a lower-bound scenario and check the next suitable product’s real operating limits.

Worked examples

Overnight 300 W load

Inputs: Average load 300 W; duration 8 h; inverter efficiency 90%; usable DOD 80%.

Calculation: Nominal energy = 300 × 8 ÷ (0.90 × 0.80) = 3,333.33333 Wh.

The estimate is 3.333 kWh nominal before product rounding and separate power checks.

Shorter workshop backup

Inputs: Average load 500 W; duration 4 h; inverter efficiency 92%; usable DOD 75%.

Calculation: Nominal energy = 500 × 4 ÷ (0.92 × 0.75) = 2,898.55072 Wh.

The model gives about 2.899 kWh. A real system needs a compatible voltage and adequate discharge-power rating.

A watt-hour requirement is converted to kilowatt-hours and then checked against voltage and current limits.
Energy sizing is one part of a complete battery selection.

Add a separate reserve decision

This formula includes the selected usable-discharge fraction, but it does not add a second standby reserve, temperature margin, or aging factor. If the manufacturer’s usable-energy rating already reflects a reserve, using that rating as the DOD percentage and applying another reduction can double-count the same constraint. Keep every margin visible in the planning sheet.

For a system with critical loads, estimate the load duration from a time profile and separate essential from optional circuits. A brief pump startup can require high power even when the average wattage is modest. The result sizes energy only; inverter continuous power, surge capability, battery current limits, protective devices, and wiring still need independent checks.

Interpret the planning result carefully

A nominal energy estimate cannot be converted directly into a guaranteed outage time. The usable fraction can change with chemistry, warranty rules, battery-management settings, temperature, and the manufacturer’s test conditions. Efficiency can also vary with power level and voltage. Use product-specific values from documentation at the relevant operating point where available.

Treat any final capacity selection as a system design question rather than a single division. Match the battery bank to DC bus voltage, current limits, charging source, inverter, protection, and applicable electrical rules. The battery capacity for backup runtime calculator gives a transparent energy estimate; it does not certify a safe configuration.

Sources and further reading