Battery capacity for backup runtime calculator
Estimate nominal battery energy required for a load and backup duration after accounting for inverter efficiency and usable depth of discharge. Enter your values below to see the result and method.
inputs.
Related calculators
These tools cover nearby questions while keeping this page focused on its own calculation.
How to use this calculator
Estimate nominal battery energy required for a load and backup duration after accounting for inverter efficiency and usable depth of discharge.
- Enter Average load (W), Backup time (hours), Inverter efficiency (%), Usable depth of discharge (%). Match the units shown beside each field and review the result together with the assumptions below.
- Read the worked example below to check the expected input format and result.
- Compare another scenario by changing one input at a time. Use Reset to return to the starting values.
Define the component and operating point
Estimate battery-side nominal energy for a stated load and backup duration. Efficiency and usable depth of discharge increase the required nameplate energy beyond load × time.
Inputs and units
Use average delivered load in watts and required backup duration in hours. Enter inverter efficiency and usable depth of discharge as percentages from 0 to 100; the output is nominal Wh.
- Average load (W): Average load as defined for the physical or engineering situation.
- Backup time (hours): Backup time as defined for the physical or engineering situation.
- Inverter efficiency (%): Inverter efficiency as defined for the physical or engineering situation.
- Usable depth of discharge (%): Usable depth of discharge as defined for the physical or engineering situation.
Design equation and example
E = load × time ÷ (η × DoD)
A 300 W load for 8 hours at 90% inverter efficiency and 80% usable capacity needs about 3.33 kWh nominal.
Intermediate values are kept unrounded; the displayed result is rounded for readability.
Applying the result in a system
Treat this as a calculation for the stated component and operating point. Real installations can add losses, tolerances, boundary conditions, or code requirements beyond this model.
Assumptions and limitations
Planning estimate; battery voltage, temperature, aging, discharge rate, reserve, and surge loads may increase required capacity.
Method reference: DOE/NREL energy-storage O&M guide: usable capacity and depth of discharge.
Frequently asked questions
Which measurements belong in the battery capacity for backup runtime?
Enter average delivered load power and backup duration; inverter efficiency and usable depth of discharge are percentages from 0 to 100. The result is nominal energy in Wh, not amp-hours.
What can make a real installation differ from this battery capacity for backup runtime estimate?
Planning estimate; battery voltage, temperature, aging, discharge rate, reserve, and surge loads may increase required capacity.
When is the battery energy from voltage and capacity more useful than the battery capacity for backup runtime?
Use the voltage-and-capacity tool when nominal voltage and amp-hours are known and you want their Wh equivalent. This page works backward from load and runtime, then accounts for efficiency and usable depth of discharge.
How do I use the Battery capacity for backup runtime calculator?
Enter Average load (W), Backup time (hours), Inverter efficiency (%), Usable depth of discharge (%). Match the units shown beside each field and review the result together with the assumptions below.
What is a worked example of Battery capacity for backup runtime?
E = load × time ÷ (η × DoD) A 300 W load for 8 hours at 90% inverter efficiency and 80% usable capacity needs about 3.33 kWh nominal. Intermediate values are kept unrounded; the displayed result is rounded for readability.