Battery Round-Trip Efficiency: Compare Energy In and Out

Battery round-trip efficiency compares energy delivered during discharge with energy supplied during charge over a matched cycle. It is not the same as state of health or the battery’s one-way conversion efficiency. Use the battery round-trip efficiency calculator to calculate the ratio and the energy difference from two kWh readings.

Open calculator
A battery charge and discharge flow diagram compares input and returned kilowatt-hours and highlights the energy difference.

Share this article

Charge energy enters a battery system, discharge energy leaves, and the difference is labeled as measured loss.
Round-trip efficiency compares energy across a selected boundary.

Choose one measurement boundary

Enter charge energy and discharge energy in kWh for the same system boundary and a complete, matched cycle. The charge reading must be positive, and the discharge reading cannot exceed it in this estimate. Decide whether meters are on the battery DC side or at the AC connection, then use the same boundary in both directions.

Round-trip efficiency (%) = discharge energy ÷ charge energy × 100. Energy loss = charge energy − discharge energy. If 100 kWh enters the selected boundary and 90 kWh comes back out, the calculated ratio is 90% and the difference is 10 kWh. The equation compares energy, not amp-hours or instantaneous power.

Match the beginning and end state

A meaningful cycle begins and ends at comparable states of charge. If discharge starts from a fuller state than charge measurement includes, or stops at a different endpoint, the ratio can mix stored energy with conversion losses. NREL’s performance-test procedure repeats cycling and checks state-of-charge consistency precisely because cycle boundaries affect the reported metric.

Keep auxiliary loads inside or outside the measurement boundary consistently. Fans, controls, standby draw, inverters, transformers, and wiring may be included if the meters are placed outside them. The calculator does not ask where meters sit, so describe that choice when sharing the result. Two values from different devices or billing intervals do not form a valid matched pair.

Interpret efficiency and absolute loss

The percent is useful for comparing ratios, while the kWh difference quantifies energy not returned across the chosen boundary. A 10 kWh loss on a 100 kWh input is 10%; a 5 kWh loss on a 50 kWh input is also 10%. The same percentage does not mean the systems lose the same absolute amount of energy.

The result is rounded to two decimal places for efficiency and three for energy loss. Preserve the meter readings and interval alongside the displayed values. If values are rounded before entry, the output can differ slightly from a ratio calculated with raw meter data. Use unrounded measurement records where the measurement system provides them.

Check two complete-cycle examples

With 100 kWh charged and 90 kWh discharged, the ratio is 90 ÷ 100 × 100 = 90%, and the energy difference is 10 kWh. With 50 kWh charged and 42 kWh discharged, the ratio is 84% and the loss is 8 kWh. Both examples use positive charging energy and a discharge result no larger than input.

An efficiency result over 100% is rejected by the runtime guard because discharge cannot exceed charge for this estimate. If a meter pair appears to do so, check interval alignment, sign conventions, state-of-charge drift, meter accuracy, and whether on-site generation or auxiliary energy entered only one side. Do not force an unusual observation into the calculator by changing the measurement boundary.

A matched charge and discharge cycle begins and ends at comparable states of charge before efficiency is calculated.
Comparable cycle endpoints help keep the ratio meaningful.

Worked examples

Grid storage cycle

Inputs: Energy supplied during charge 100 kWh; returned during discharge 90 kWh.

Calculation: RTE = 90 ÷ 100 × 100 = 90%; loss = 100 − 90 = 10 kWh.

Round-trip efficiency is 90.00%, and the measured boundary shows 10.000 kWh not returned.

Smaller matched cycle

Inputs: Energy supplied during charge 50 kWh; returned during discharge 42 kWh.

Calculation: RTE = 42 ÷ 50 × 100 = 84%; loss = 50 − 42 = 8 kWh.

The ratio is 84.00%; the absolute difference is 8.000 kWh for this cycle.

Use RTE as a measured system metric

Efficiency varies with power level, temperature, state of charge, standby time, controls, and where measurements are made. One cycle is not necessarily representative of annual operation. NREL distinguishes nominal-power testing from other discharge-rate tests and specifies matched start/end conditions; an operational metric should state its test conditions.

Use the calculator for a transparent ratio and loss estimate, then compare results only when cycle protocol and system boundary match. RTE does not measure battery capacity, available power, life expectancy, or safety. For investment or performance guarantees, follow the applicable test procedure and report meter locations, load profile, temperature, and state-of-charge limits.