How to use this calculator
Find the equilibrium outlet of an insulated air-water contactor when makeup liquid enters at the outlet temperature.
- Enter Unsaturated inlet dry-bulb temperature (°C), Inlet humidity ratio (kg/kg dry air), Total absolute air pressure (Pa), Dry-air flow (kg/s). Match the units shown beside each field and review the result together with the assumptions below.
- Read the worked example below to check the expected input format and result.
- Compare another scenario by changing one input at a time. Use Reset to return to the starting values.
Adiabatic air saturator with recirculated liquid explained
A numerical walkthrough
Unsaturated inlet dry-bulb temperature (°C) = 35; Inlet humidity ratio (kg/kg dry air) = 0.008; Total absolute air pressure (Pa) = 101325; Dry-air flow (kg/s) = 1.
- Adiabatic saturation temperature: 19.657681 °C
- Saturated outlet humidity ratio: 0.014379 kg/kg dry air
- Evaporated liquid flow: 0.006379 kg/s
Dry air flow 1 kg/s enters at 35 °C and humidity ratio 0.008. With recirculated liquid at the final saturation temperature and pressure 101,325 Pa, the balance reaches 19.6577 °C, humidity ratio 0.0143792 and 0.00637919 kg/s evaporation.
The model behind the numbers
hin+(ws,out−win)cp,water Tout=hout(Tout,ws,out), with ws=0.621945 Psat/(p−Psat).
Solve coupled saturation and energy balances rather than imposing constant moist-air enthalpy. The added liquid’s sensible enthalpy is retained on the 0 °C liquid-water reference.
What to enter
Ti— Unsaturated inlet dry-bulb temperature (°C)- Unsaturated inlet dry-bulb temperature (°C). Enter the value for this state; the units shown are used without an unstated conversion.
wi— Inlet humidity ratio (kg/kg dry air)- Inlet humidity ratio (kg/kg dry air). Enter the value for this state; the units shown are used without an unstated conversion.
p— Total absolute air pressure (Pa)- Total absolute air pressure (Pa). Enter the value for this state; the units shown are used without an unstated conversion.
m— Dry-air flow (kg/s)- Dry-air flow (kg/s). Enter the value for this state; the units shown are used without an unstated conversion.
Interpreting the result
Ideal moist air and liquid-water contact at 0–80 °C inlet; no subzero ice saturation, drift droplets, heat leakage or finite contactor effectiveness.
Reading the outputs
Outlet saturation temperature is Celsius, moisture is kg/kg dry air and evaporated water is kg/s.
Frequently asked questions
Is this exactly a wet-bulb thermometer temperature?
It is the thermodynamic adiabatic saturation temperature; real thermometer heat and mass transfer can differ.
Why is the process not exactly constant enthalpy?
Evaporated makeup liquid carries sensible enthalpy into the air-water balance.
Does this predict a real evaporative cooler outlet?
It gives a saturation endpoint; a finite cooler effectiveness is needed for actual operation.
How do I use the Adiabatic air saturator with recirculated liquid calculator?
Enter Unsaturated inlet dry-bulb temperature (°C), Inlet humidity ratio (kg/kg dry air), Total absolute air pressure (Pa), Dry-air flow (kg/s). Match the units shown beside each field and review the result together with the assumptions below.
What is a worked example of Adiabatic air saturator with recirculated liquid?
Unsaturated inlet dry-bulb temperature (°C) = 35; Inlet humidity ratio (kg/kg dry air) = 0.008; Total absolute air pressure (Pa) = 101325; Dry-air flow (kg/s) = 1. Adiabatic saturation temperature: 19.657681 °C Saturated outlet humidity ratio: 0.014379 kg/kg dry air Evaporated liquid flow: 0.006379 kg/s Dry air flow 1 kg/s enters at 35 °C and humidity ratio 0.008. With recirculated liquid at the final saturation temperature and pressure 101,325 Pa, the balance reaches 19.6577 °C, humidity ratio 0.0143792 and 0.00637919 kg/s evaporation.
Background or definition reference: EnergyPlus air-system humidifier moisture and enthalpy balances.
Read our calculation methodology.