How to use this calculator
Convert dry-bulb temperature, relative humidity, and pressure into dry-air-based moisture and thermal properties.
- Enter Dry-bulb temperature (°C), Relative humidity (%), Absolute air pressure (kPa). Match the units shown beside each field and review the result together with the assumptions below.
- Read the worked example below to check the expected input format and result.
- Compare another scenario by changing one input at a time. Use Reset to return to the starting values.
Moist air humidity ratio and enthalpy explained
A numerical walkthrough
Dry-bulb temperature (°C) = 25; Relative humidity (%) = 50; Absolute air pressure (kPa) = 101.325.
- Humidity ratio: 0.0098810437 kg water/kg dry air
- Moist-air enthalpy: 50.3219588 kJ/kg dry air
- Specific moist-air volume: 0.85804326 m³/kg dry air
- Saturation-equilibrium temperature: 13.86397327 °C
At 25°C and 50% relative humidity, the vapor partial pressure is about 1.585 kPa. Dividing by the dry-air pressure basis gives a humidity ratio of about 0.009881 kg water per kg dry air.
The model behind the numbers
pv=RH·pws; W=0.621945pv/(P−pv); h=1.006T+W(2501+1.86T)
Evaluate the stated saturation-pressure correlation at dry-bulb temperature, then multiply by relative humidity to obtain water-vapor partial pressure. Convert partial pressure to dry-air humidity ratio, enthalpy, and specific volume. A bracketed inverse saturation solve gives the equilibrium saturation temperature.
What to enter
t— Dry-bulb temperature (°C)- Dry-bulb temperature (°C).
rh— Relative humidity (%)- Relative humidity (%).
p— Absolute air pressure (kPa)- Absolute air pressure (kPa).
Interpreting the result
Uses ideal moist-air relations and ASHRAE saturation-pressure correlations. Below 0.01°C the saturation reference is ice, so the inverse temperature is a frost-point equilibrium reference.
Frequently asked questions
Is humidity ratio kilograms per kilogram of moist air?
No, the denominator is dry air.
Is pressure gauge or absolute?
Absolute pressure.
Why can saturation temperature below freezing be called frost point?
The selected correlation uses equilibrium over ice below the triple-point threshold.
How do I use the Moist air humidity ratio and enthalpy calculator?
Enter Dry-bulb temperature (°C), Relative humidity (%), Absolute air pressure (kPa). Match the units shown beside each field and review the result together with the assumptions below.
What is a worked example of Moist air humidity ratio and enthalpy?
Dry-bulb temperature (°C) = 25; Relative humidity (%) = 50; Absolute air pressure (kPa) = 101.325. Humidity ratio: 0.0098810437 kg water/kg dry air Moist-air enthalpy: 50.3219588 kJ/kg dry air Specific moist-air volume: 0.85804326 m³/kg dry air Saturation-equilibrium temperature: 13.86397327 °C At 25°C and 50% relative humidity, the vapor partial pressure is about 1.585 kPa. Dividing by the dry-air pressure basis gives a humidity ratio of about 0.009881 kg water per kg dry air.
Method reference: PsychroLib ASHRAE psychrometric implementation.