How to use this calculator
Mix two air streams by dry-air and enthalpy conservation, then check whether an unsaturated vapor-only outlet is possible.
- Enter First dry-air mass flow (kg/s), Second dry-air mass flow (kg/s), First dry-bulb temperature (°C), Second dry-bulb temperature (°C), then complete the remaining labeled fields. Match the units shown beside each field and review the result together with the assumptions below.
- Read the worked example below to check the expected input format and result.
- Compare another scenario by changing one input at a time. Use Reset to return to the starting values.
Adiabatic mixing of two moist air streams explained
For two streams at the same pressure, dry-air mass flow weights the mixed humidity ratio and moist-air enthalpy. The resulting temperature is recovered from the psychrometric enthalpy relation, so neither temperature nor relative humidity should be averaged directly.
Inputs, symbols, and units
m1— First dry-air mass flow (kg/s)- First dry-air mass flow (kg/s).
m2— Second dry-air mass flow (kg/s)- Second dry-air mass flow (kg/s).
t1— First dry-bulb temperature (°C)- First dry-bulb temperature (°C).
t2— Second dry-bulb temperature (°C)- Second dry-bulb temperature (°C).
w1— First humidity ratio (kg/kg dry air)- First humidity ratio (kg/kg dry air).
w2— Second humidity ratio (kg/kg dry air)- Second humidity ratio (kg/kg dry air).
p— Common absolute pressure (kPa)- Common absolute pressure (kPa).
Formula and method
Dry-air mass-weighted W and h; solve mixed T from h
Weight humidity ratio and moist-air enthalpy by dry-air mass flow, not by total humid-air mass. Solve the mixed enthalpy expression for dry-bulb temperature. Recompute relative humidity and reject a vapor-only result above saturation, where condensation would change the balance.
A worked scenario
First dry-air mass flow (kg/s) = 1; Second dry-air mass flow (kg/s) = 2; First dry-bulb temperature (°C) = 10; Second dry-bulb temperature (°C) = 30; First humidity ratio (kg/kg dry air) = 0.004; Second humidity ratio (kg/kg dry air) = 0.014; Common absolute pressure (kPa) = 101.325.
- Mixed dry-bulb temperature: 23.4139177 °C
- Mixed humidity ratio: 0.0106666667 kg/kg dry air
- Mixed enthalpy: 50.69626667 kJ/kg dry air
- Mixed relative humidity: 59.28836482 %
This scenario uses the stated units and assumptions. Displayed values are rounded only after calculation.
Assumptions and edge cases
No heat exchange, fan heat, or liquid droplets. Supersaturated calculated mixtures are rejected because condensation requires another energy-and-phase balance.
Frequently asked questions
Should flow be moist-air mass flow?
No, use dry-air mass flow for both streams.
Can the arithmetic temperature average be used?
Only under simplifying equal heat-capacity weighting; this tool conserves moist-air enthalpy.
What if the mixture condenses?
This vapor-only model reports that its assumption fails.
How do I use the Adiabatic mixing of two moist air streams calculator?
Enter First dry-air mass flow (kg/s), Second dry-air mass flow (kg/s), First dry-bulb temperature (°C), Second dry-bulb temperature (°C), then complete the remaining labeled fields. Match the units shown beside each field and review the result together with the assumptions below.
What is a worked example of Adiabatic mixing of two moist air streams?
First dry-air mass flow (kg/s) = 1; Second dry-air mass flow (kg/s) = 2; First dry-bulb temperature (°C) = 10; Second dry-bulb temperature (°C) = 30; First humidity ratio (kg/kg dry air) = 0.004; Second humidity ratio (kg/kg dry air) = 0.014; Common absolute pressure (kPa) = 101.325. Mixed dry-bulb temperature: 23.4139177 °C Mixed humidity ratio: 0.0106666667 kg/kg dry air Mixed enthalpy: 50.69626667 kJ/kg dry air Mixed relative humidity: 59.28836482 % This scenario uses the stated units and assumptions. Displayed values are rounded only after calculation.
Read our calculation methodology.