Adiabatic liquid pump work and dissipative heating calculator — Inlet absolute pressure (kPa), Outlet absolute pressure (kPa), Liquid density (kg/m³) and calculation method
Adiabatic liquid pump work and dissipative heating calculator: inputs and calculation method.

How to use this calculator

Separate useful pressure energy from the extra shaft work that heats a liquid in an imperfect pump.

  1. Enter Inlet absolute pressure (kPa), Outlet absolute pressure (kPa), Liquid density (kg/m³), Liquid specific heat (kJ/kg/K), then complete the remaining labeled fields. Match the units shown beside each field and review the result together with the assumptions below.
  2. Read the worked example below to check the expected input format and result.
  3. Compare another scenario by changing one input at a time. Use Reset to return to the starting values.
Calculation guide

Adiabatic liquid pump work and dissipative heating explained

For an incompressible liquid, pressure rise sets ideal pump work; the efficiency shortfall becomes approximate heat in this adiabatic model.

Shaft work per mass1.2024kJ/kg
Shaft work per mass: 1.202405 kJ/kg in the worked scenario.

How the calculation works

wis=vΔp; w=wis/η; ΔT≈(w−vΔp)/cp for an adiabatic incompressible pump.

Use an incompressible enthalpy increment dh≈cp dT+v dp. The excess above ideal pressure work becomes sensible heating in this adiabatic approximation.

Set up the calculation

p1 — Inlet absolute pressure (kPa)
Inlet absolute pressure (kPa). Enter the value for this state; the units shown are used without an unstated conversion.
p2 — Outlet absolute pressure (kPa)
Outlet absolute pressure (kPa). Enter the value for this state; the units shown are used without an unstated conversion.
rho — Liquid density (kg/m³)
Liquid density (kg/m³). Enter the value for this state; the units shown are used without an unstated conversion.
cp — Liquid specific heat (kJ/kg/K)
Liquid specific heat (kJ/kg/K). Enter the value for this state; the units shown are used without an unstated conversion.
eta — Pump hydraulic efficiency
Pump hydraulic efficiency. Enter the value for this state; the units shown are used without an unstated conversion.
m — Liquid mass flow (kg/s)
Liquid mass flow (kg/s). Enter the value for this state; the units shown are used without an unstated conversion.

Limits of this model

Constant density and cp; neglect liquid thermal expansion and isentropic temperature change, velocity/elevation changes, motor heat and casing heat loss.

Check this example

Inlet absolute pressure (kPa) = 100; Outlet absolute pressure (kPa) = 1000; Liquid density (kg/m³) = 998; Liquid specific heat (kJ/kg/K) = 4.18; Pump hydraulic efficiency = 0.75; Liquid mass flow (kg/s) = 2.

  • Shaft work per mass: 1.202405 kJ/kg
  • Approximate dissipative temperature rise: 0.071914 K
  • Shaft power: 2.40481 kW

Raising a 998 kg/m³ liquid from 100 to 1,000 kPa at 75% efficiency requires 1.20240 kJ/kg shaft work. Only its dissipative excess produces the 0.071914 K temperature rise; at 2 kg/s shaft power is 2.40481 kW.

Reading the outputs

Returns work in kJ/kg, dissipative temperature rise in kelvin and shaft power in kW.

Frequently asked questions

Is this the motor electrical input?

No. Include motor and drive efficiencies separately.

Why does ideal efficiency give zero heating?

The incompressible approximation assigns all ideal work to pressure rise and neglects thermoelastic temperature change.

Does pressure rise alone equal a large temperature rise?

Not for a nearly incompressible liquid; most ideal work appears as pressure energy.

How do I use the Adiabatic liquid pump work and dissipative heating calculator?

Enter Inlet absolute pressure (kPa), Outlet absolute pressure (kPa), Liquid density (kg/m³), Liquid specific heat (kJ/kg/K), then complete the remaining labeled fields. Match the units shown beside each field and review the result together with the assumptions below.

What is a worked example of Adiabatic liquid pump work and dissipative heating?

Inlet absolute pressure (kPa) = 100; Outlet absolute pressure (kPa) = 1000; Liquid density (kg/m³) = 998; Liquid specific heat (kJ/kg/K) = 4.18; Pump hydraulic efficiency = 0.75; Liquid mass flow (kg/s) = 2. Shaft work per mass: 1.202405 kJ/kg Approximate dissipative temperature rise: 0.071914 K Shaft power: 2.40481 kW Raising a 998 kg/m³ liquid from 100 to 1,000 kPa at 75% efficiency requires 1.20240 kJ/kg shaft work. Only its dissipative excess produces the 0.071914 K temperature rise; at 2 kg/s shaft power is 2.40481 kW.