How to use this calculator
Calculate classical Cohen-Coon PID settings from a first-order-plus-dead-time process reaction curve.
- Enter Process gain, Kp, Process time constant, τ (s), Process dead time, θ (s). Match the units shown beside each field and review the result together with the assumptions below.
- Read the worked example below to check the expected input format and result.
- Compare another scenario by changing one input at a time. Use Reset to return to the starting values.
How this calculation works
The Cohen-Coon open-loop method maps a first-order-plus-dead-time process model to proportional, integral, and derivative settings. It uses the identified process gain, time constant, and apparent dead time from a reaction curve.
Inputs and units
processGain— Process gain, Kp- Steady process output change per unit manipulated-input change.
timeConstant— Process time constant, τ (s)- First-order time constant from the fitted process model.
deadTime— Process dead time, θ (s)- Apparent reaction-curve dead time in the same time unit as τ.
Formula
Kc = (τ/(Kpθ))(4/3 + θ/(4τ)); Ti = θ(32 + 6θ/τ)/(13 + 8θ/τ); Td = 4θ/(11 + 2θ/τ).
Method
Enter positive process gain Kp, process time constant τ, and dead time θ in consistent time units. The calculator reports the ideal/parallel PID proportional gain Kc and integral and derivative times.
Worked example
For Kp = 2, τ = 10 s, and θ = 2 s, the classical Cohen-Coon PID settings are Kc = 3.4583, Ti = 4.5479 s, and Td = 0.7018 s.
Assumptions and limits
Cohen-Coon settings are a model-based starting point, not a guarantee of robust closed-loop behavior. Dead-time identification, actuator limits, noise, nonlinearities, and process safety matter; validate conservatively on the actual loop.
Frequently asked questions
What process model does Cohen-Coon use?
It uses an open-loop first-order-plus-dead-time model estimated from a process reaction curve.
Are these settings guaranteed to be stable?
No. They are tuning estimates that must be checked against the real plant and its operating constraints.
Which PID form is reported?
The reported Kc, Ti, and Td correspond to the ideal/parallel form Kc[1 + 1/(Ti s) + Td s].
How do I use the Cohen-Coon PID Tuning Calculator?
Enter Process gain, Kp, Process time constant, τ (s), Process dead time, θ (s). Match the units shown beside each field and review the result together with the assumptions below.
What is a worked example of Cohen-Coon PID Tuning?
For Kp = 2, τ = 10 s, and θ = 2 s, the classical Cohen-Coon PID settings are Kc = 3.4583, Ti = 4.5479 s, and Td = 0.7018 s.
Reference: NI Cohen-Coon autotuning method and PID settings. See our calculation methodology.