Ultimate gain Ziegler Nichols PID tuning calculator — Ultimate proportional gain, Ultimate oscillation period (s) and calculation method
Ultimate gain Ziegler Nichols PID tuning calculator: inputs and calculation method.

How to use this calculator

Translate a measured ultimate gain and oscillation period into the classic Ziegler–Nichols PID starting settings.

  1. Enter Ultimate proportional gain, Ultimate oscillation period (s). Match the units shown beside each field and review the result together with the assumptions below.
  2. Read the worked example below to check the expected input format and result.
  3. Compare another scenario by changing one input at a time. Use Reset to return to the starting values.
Calculation guide

Ultimate gain Ziegler Nichols PID tuning explained

Proportional gain2.4gain
Proportional gain: 2.4 gain in the worked scenario.

How the calculation works

Classic ideal PID: Kc=0.6Ku, Ti=Pu/2, Td=Pu/8; C(s)=Kc[1+1/(Ti s)+Td s].

Use the original ideal controller convention. These empirical values can be aggressive; they do not perform a safe ultimate-gain experiment for you.

Set up the calculation

Ku — Ultimate proportional gain
Positive gain at sustained small-signal closed-loop oscillation.
Pu — Ultimate oscillation period (s)
Period measured at that limiting oscillation.

Limits of this model

Requires meaningful sustained linear oscillation data. Do not apply the rule blindly to unsafe, noisy or highly nonlinear equipment.

Check this example

Ultimate proportional gain = 4; Ultimate oscillation period (s) = 6.

  • Proportional gain: 2.4 gain
  • Integral time: 3 s
  • Derivative time: 0.75 s
  • Parallel integral gain: 0.8 gain/s

A test identifies ultimate gain four and a six-second oscillation period; compute ideal-form proportional, integral and derivative settings.

Reading the outputs

Integral and derivative times are seconds; the extra Ki metric helps map to a parallel controller.

Frequently asked questions

Is Ti the integral gain?

No; integral gain is Kc/Ti.

Does this account for derivative filtering?

No. A real controller normally needs a separately selected derivative filter.

What if the plant never has an ultimate oscillation?

This rule is not applicable; use a model-based method.

How do I use the Ultimate gain Ziegler Nichols PID tuning calculator?

Enter Ultimate proportional gain, Ultimate oscillation period (s). Match the units shown beside each field and review the result together with the assumptions below.

What is a worked example of Ultimate gain Ziegler Nichols PID tuning?

Ultimate proportional gain = 4; Ultimate oscillation period (s) = 6. Proportional gain: 2.4 gain Integral time: 3 s Derivative time: 0.75 s Parallel integral gain: 0.8 gain/s A test identifies ultimate gain four and a six-second oscillation period; compute ideal-form proportional, integral and derivative settings.