CalcWorldHub
Free online calculator · no signup

Cooling-coil bypass factor and condensate balance calculator

Estimate a wet cooling coil’s leaving air state and condensate removal from its apparatus dew point and bypass factor.

4,000 tools
Cooling-coil bypass factor and condensate balance calculator — Inlet dry-bulb temperature (°C), Inlet humidity ratio (kg/kg dry air), Apparatus dew-point temperature (°C) and calculation method
Cooling-coil bypass factor and condensate balance calculator: inputs and calculation method.

How to use this calculator

Estimate a wet cooling coil’s leaving air state and condensate removal from its apparatus dew point and bypass factor.

  1. Enter Inlet dry-bulb temperature (°C), Inlet humidity ratio (kg/kg dry air), Apparatus dew-point temperature (°C), Saturated humidity ratio at apparatus dew point (kg/kg dry air), then complete the remaining labeled fields. Match the units shown beside each field and review the result together with the assumptions below.
  2. Read the worked example below to check the expected input format and result.
  3. Compare another scenario by changing one input at a time. Use Reset to return to the starting values.
Calculation guide

Cooling-coil bypass factor and condensate balance explained

The bypass-factor model mixes inlet air with the apparatus-dew-point state to estimate outlet humidity, condensate and approximate cooling duty.

Leaving dry-bulb temperature13°C
Leaving dry-bulb temperature: 13 °C in the worked scenario.

How the calculation works

Tout=Tadp+BF(Tin−Tadp); wout=wadp+BF(win−wadp); mcond=mdry(win−wout).

Treat leaving air as a mixture of untreated bypass air and air brought to the apparatus dew-point state. Enter wadp from verified saturation properties at the stated dew point and pressure.

Set up the calculation

Ti — Inlet dry-bulb temperature (°C)
Inlet dry-bulb temperature (°C). Enter the value for this state; the units shown are used without an unstated conversion.
wi — Inlet humidity ratio (kg/kg dry air)
Inlet humidity ratio (kg/kg dry air). Enter the value for this state; the units shown are used without an unstated conversion.
Tb — Apparatus dew-point temperature (°C)
Apparatus dew-point temperature (°C). Enter the value for this state; the units shown are used without an unstated conversion.
wb — Saturated humidity ratio at apparatus dew point (kg/kg dry air)
Saturated humidity ratio at apparatus dew point (kg/kg dry air). Enter the value for this state; the units shown are used without an unstated conversion.
bf — Coil bypass factor
Coil bypass factor. Enter the value for this state; the units shown are used without an unstated conversion.
m — Dry-air mass flow (kg/s)
Dry-air mass flow (kg/s). Enter the value for this state; the units shown are used without an unstated conversion.

Limits of this model

Ideal straight-line bypass model with supplied dew-point humidity ratio. Cooling duty neglects condensate sensible enthalpy, fan heat and pressure drop; no frost or partially wet coil model.

Check this example

Inlet dry-bulb temperature (°C) = 30; Inlet humidity ratio (kg/kg dry air) = 0.014; Apparatus dew-point temperature (°C) = 10; Saturated humidity ratio at apparatus dew point (kg/kg dry air) = 0.00763; Coil bypass factor = 0.15; Dry-air mass flow (kg/s) = 1.

  • Leaving dry-bulb temperature: 13 °C
  • Leaving humidity ratio: 0.008585 kg/kg dry air
  • Condensate mass flow: 0.005415 kg/s
  • Approximate air-side cooling duty: 31.217267 kW

Air at 30 °C and humidity ratio 0.014 approaches a 10 °C apparatus-dew-point state with humidity ratio 0.00763 through a coil with 15% bypass. Outlet air is 13 °C and 0.0085855 kg/kg dry air; at 1 kg/s dry air, condensate is 0.0054145 kg/s.

Reading the outputs

Reports leaving temperature, leaving moisture per dry-air mass, condensate rate and moist-air enthalpy reduction in kW.

Frequently asked questions

Is bypass factor an air leakage fraction?

It is an effective heat/mass-transfer parameter; it need not equal a literal leaking air fraction.

What happens at BF=1?

The air leaves unchanged and the predicted duty and condensate are zero.

Why must apparatus dew-point humidity be supplied?

It depends on pressure and saturation temperature; use a consistent property source.

How do I use the Cooling-coil bypass factor and condensate balance calculator?

Enter Inlet dry-bulb temperature (°C), Inlet humidity ratio (kg/kg dry air), Apparatus dew-point temperature (°C), Saturated humidity ratio at apparatus dew point (kg/kg dry air), then complete the remaining labeled fields. Match the units shown beside each field and review the result together with the assumptions below.

What is a worked example of Cooling-coil bypass factor and condensate balance?

Inlet dry-bulb temperature (°C) = 30; Inlet humidity ratio (kg/kg dry air) = 0.014; Apparatus dew-point temperature (°C) = 10; Saturated humidity ratio at apparatus dew point (kg/kg dry air) = 0.00763; Coil bypass factor = 0.15; Dry-air mass flow (kg/s) = 1. Leaving dry-bulb temperature: 13 °C Leaving humidity ratio: 0.008585 kg/kg dry air Condensate mass flow: 0.005415 kg/s Approximate air-side cooling duty: 31.217267 kW Air at 30 °C and humidity ratio 0.014 approaches a 10 °C apparatus-dew-point state with humidity ratio 0.00763 through a coil with 15% bypass. Outlet air is 13 °C and 0.0085855 kg/kg dry air; at 1 kg/s dry air, condensate is 0.0054145 kg/s.