How to use this calculator
Calculate log mean temperature difference for a counterflow heat exchanger from four terminal temperatures.
- Enter Hot stream inlet temperature (°C), Hot stream outlet temperature (°C), Cold stream inlet temperature (°C), Cold stream outlet temperature (°C). Match the units shown beside each field and review the result together with the assumptions below.
- Read the worked example below to check the expected input format and result.
- Compare another scenario by changing one input at a time. Use Reset to return to the starting values.
How this calculation works
The log mean temperature difference condenses the changing hot-to-cold temperature gap along a counterflow exchanger into one effective driving temperature difference. It is used with heat-transfer area and an overall heat-transfer coefficient in a basic exchanger duty relation.
Inputs and units
hotIn— Hot stream inlet temperature (°C)- Hot-fluid temperature entering the exchanger.
hotOut— Hot stream outlet temperature (°C)- Hot-fluid temperature leaving the exchanger.
coldIn— Cold stream inlet temperature (°C)- Cold-fluid temperature entering the exchanger.
coldOut— Cold stream outlet temperature (°C)- Cold-fluid temperature leaving the exchanger.
Formula
ΔT₁ = Tₕ,in − T꜀, out; ΔT₂ = Tₕ,out − T꜀, in. LMTD = (ΔT₁ − ΔT₂) / ln(ΔT₁/ΔT₂); if ΔT₁ = ΔT₂, LMTD = ΔT₁.
Method
Enter hot- and cold-stream inlet and outlet temperatures using one consistent temperature scale. Both counterflow terminal differences must be positive; equal terminal differences use their common value as the limit.
Worked example
For hot stream 500°C in and 400°C out, and cold stream 120°C in and 310°C out, the counterflow terminal differences are 190°C and 280°C. LMTD = (280−190)/ln(280/190) ≈ 232.1°C.
Assumptions and limits
This is the ideal counterflow terminal-temperature calculation. It does not apply a multipass or crossflow correction factor, determine heat capacity rates, or verify an energy balance. For equipment design, confirm flow arrangement, phase changes, fouling, and applicable correction factors.
Frequently asked questions
Why must both terminal differences be positive?
A non-positive terminal difference would imply a temperature crossing or an invalid counterflow pairing under this simple model.
What if the two terminal differences are equal?
The logarithmic expression has a finite limit equal to that common difference; the calculator uses that limit.
Can I use this for a multipass exchanger?
The base LMTD can be a starting point, but many multipass arrangements need a correction factor based on their flow configuration.
Can Celsius and Fahrenheit be mixed?
No. Enter all four temperatures on the same scale. A temperature difference in °C and in K has the same numeric size.
How do I use the Counterflow heat exchanger LMTD calculator?
Enter Hot stream inlet temperature (°C), Hot stream outlet temperature (°C), Cold stream inlet temperature (°C), Cold stream outlet temperature (°C). Match the units shown beside each field and review the result together with the assumptions below.
Reference: U.S. Department of Energy fundamentals handbook LMTD example. See our calculation methodology.