Multilayer wall film and contact temperature profile calculator

Check both room-side and exterior surface temperatures of a layered wall while retaining convection and contact resistance.

4,000 tools
Multilayer wall film and contact temperature profile calculator — Layer thicknesses from indoors to outdoors (m), Layer thermal conductivities (W/m/K), Interlayer contact resistances (m² K/W) and calculation method
Multilayer wall film and contact temperature profile calculator: inputs and calculation method.

How to use this calculator

Check both room-side and exterior surface temperatures of a layered wall while retaining convection and contact resistance.

  1. Enter Layer thicknesses from indoors to outdoors (m), Layer thermal conductivities (W/m/K), Interlayer contact resistances (m² K/W), Indoor film coefficient (W/m²/K), then complete the remaining labeled fields. Match the units shown beside each field and review the result together with the assumptions below.
  2. Read the worked example below to check the expected input format and result.
  3. Compare another scenario by changing one input at a time. Use Reset to return to the starting values.
Calculation guide

Multilayer wall film and contact temperature profile explained

For steady one-dimensional heat flow, each layer, surface film, and contact resistance contributes to the total thermal resistance. Ordered thicknesses and conductivities set the temperature drops; the calculated profile assumes no lateral heat flow, heat storage, or internal generation.

Signed through-wall heat flux8.5616W/m²
Signed through-wall heat flux: 8.561644 W/m² in the worked scenario.

Inputs, symbols, and units

t — Layer thicknesses from indoors to outdoors (m)
Enter each solid thickness in order along the heat path. Use comma-separated values in the stated order.
k — Layer thermal conductivities (W/m/K)
One positive conductivity per thickness, in the identical order. Use comma-separated values in the stated order.
rc — Interlayer contact resistances (m² K/W)
One nonnegative area-specific contact resistance between each adjacent pair of layers; use zero for perfect contact. Use comma-separated values in the stated order.
hi — Indoor film coefficient (W/m²/K)
Indoor film coefficient (W/m²/K). Enter the value for this state; the units shown are used without an unstated conversion.
ho — Outdoor film coefficient (W/m²/K)
Outdoor film coefficient (W/m²/K). Enter the value for this state; the units shown are used without an unstated conversion.
Ti — Indoor bulk temperature (°C)
Indoor bulk temperature (°C). Enter the value for this state; the units shown are used without an unstated conversion.
To — Outdoor bulk temperature (°C)
Outdoor bulk temperature (°C). Enter the value for this state; the units shown are used without an unstated conversion.
A — Wall area (m²)
Wall area (m²). Enter the value for this state; the units shown are used without an unstated conversion.

Formula and method

R″total=1/hi+Σ(tj/kj)+ΣRc,j+1/ho; q″=(Ti−To)/R″total; Tsi=Ti−q″/hi, Tso=To+q″/ho.

Assemble an ordered per-area resistance network. Surface temperatures use bulk-to-wall film drops, so they cannot be read directly from the room and outdoor temperatures.

A worked scenario

Layer thicknesses from indoors to outdoors (m) = [0.02, 0.1, 0.1]; Layer thermal conductivities (W/m/K) = [0.2, 0.04, 0.8]; Interlayer contact resistances (m² K/W) = [0.01, 0.02]; Indoor film coefficient (W/m²/K) = 8; Outdoor film coefficient (W/m²/K) = 25; Indoor bulk temperature (°C) = 20; Outdoor bulk temperature (°C) = -5; Wall area (m²) = 10.

  • Signed through-wall heat flux: 8.561644 W/m²
  • Signed wall heat rate: 85.616438 W
  • Indoor wall-surface temperature: 18.929795 °C
  • Outdoor wall-surface temperature: -4.657534 °C

A 10 m² three-layer wall with the entered 0.02, 0.1 and 0.1 m layers, two contact resistances and 20/−5 °C bulk temperatures transmits 85.6164 W. Indoor surface temperature is 18.9298 °C, so a bulk-air difference alone would overstate the solid-face drop.

Assumptions and edge cases

Steady one-dimensional layers, constant properties, no heat sources, thermal bridges, radiation exchange or moisture transport.

Reading the outputs

Flux and heat rate are positive indoors to outdoors. The two surface temperatures describe possible comfort or condensation-sensitive surfaces, without calculating moisture risk.

Frequently asked questions

Why must contact resistance use m² K/W?

The network is per unit common wall area; a resistance in K/W must first be multiplied by the corresponding area.

Does this replace the existing two-layer resistance tool?

It handles ordered multiple layers, interface contacts and both film surface temperatures; the simple tool remains useful for a bare two-layer solid resistance.

Can heat flow inward?

Yes. Reversing the bulk temperature difference reverses the signed heat flux and surface film drops.

How do I use the Multilayer wall film and contact temperature profile calculator?

Enter Layer thicknesses from indoors to outdoors (m), Layer thermal conductivities (W/m/K), Interlayer contact resistances (m² K/W), Indoor film coefficient (W/m²/K), then complete the remaining labeled fields. Match the units shown beside each field and review the result together with the assumptions below.

What is a worked example of Multilayer wall film and contact temperature profile?

Layer thicknesses from indoors to outdoors (m) = [0.02, 0.1, 0.1]; Layer thermal conductivities (W/m/K) = [0.2, 0.04, 0.8]; Interlayer contact resistances (m² K/W) = [0.01, 0.02]; Indoor film coefficient (W/m²/K) = 8; Outdoor film coefficient (W/m²/K) = 25; Indoor bulk temperature (°C) = 20; Outdoor bulk temperature (°C) = -5; Wall area (m²) = 10. Signed through-wall heat flux: 8.561644 W/m² Signed wall heat rate: 85.616438 W Indoor wall-surface temperature: 18.929795 °C Outdoor wall-surface temperature: -4.657534 °C A 10 m² three-layer wall with the entered 0.02, 0.1 and 0.1 m layers, two contact resistances and 20/−5 °C bulk temperatures transmits 85.6164 W.