Quadratic pump system operating point calculator

Intersect a falling quadratic pump curve with a rising static-plus-friction system curve.

4,000 tools
Quadratic pump system operating point calculator — Pump shutoff head (m), Pump head-curve coefficient (m/(L/s)²), System static head (m) and calculation method
Quadratic pump system operating point calculator: inputs and calculation method.

How to use this calculator

Intersect a falling quadratic pump curve with a rising static-plus-friction system curve.

  1. Enter Pump shutoff head (m), Pump head-curve coefficient (m/(L/s)²), System static head (m), System resistance coefficient (m/(L/s)²). Match the units shown beside each field and review the result together with the assumptions below.
  2. Read the worked example below to check the expected input format and result.
  3. Compare another scenario by changing one input at a time. Use Reset to return to the starting values.
Calculation guide

Quadratic pump system operating point explained

The operating point is the flow where the pump head curve meets the head required by the system curve.

Curve-intersection flow10L/s
Curve-intersection flow: 10 L/s in the worked scenario.

How the calculation works

sqrt((h0-hs)/(a+k))

Q is flow in L/s; h0 and hs are zero-flow and static head, while a and k define the pump and system curves. Hump-free quadratic approximation over the valid pump range; no efficiency, cavitation, motor, or stability assessment is performed..

Set up the calculation

h0 — Pump shutoff head (m)
Pump head at zero flow on the assumed quadratic curve. It must exceed static head for a positive-flow intersection.
a — Pump head-curve coefficient (m/(L/s)²)
Coefficient a in H_pump=h0−aQ²; flow is measured in L/s, so this unit makes the head term metres.
hs — System static head (m)
Required elevation or pressure head at zero flow; it is the vertical offset of the system curve.
k — System resistance coefficient (m/(L/s)²)
Coefficient k in H_system=hs+kQ²; it represents the modeled piping resistance over the entered flow range.

Limits of this model

Hump-free quadratic approximation over the valid pump range; no efficiency, cavitation, motor, or stability assessment is performed.

Check this example

Pump shutoff head (m) = 40; Pump head-curve coefficient (m/(L/s)²) = 0.1; System static head (m) = 10; System resistance coefficient (m/(L/s)²) = 0.2.

  • Curve-intersection flow: 10 L/s
  • Operating head: 30 m

The two curves intersect at 10 L/s and 30 m head. This is the modeled operating point; efficiency, cavitation and motor limits are outside the calculation.

Interpreting the result

A positive intersection gives the modeled flow and head within the pump curve’s valid range; it does not establish efficiency, cavitation margin or motor suitability.

Frequently asked questions

What if static head exceeds shutoff head?

No positive-flow operating point exists in this model.

Are the coefficient units important?

Yes, both use flow in L/s.

Does it choose a pump model?

No, enter fitted curves for your candidate.

How do I use the Quadratic pump system operating point calculator?

Enter Pump shutoff head (m), Pump head-curve coefficient (m/(L/s)²), System static head (m), System resistance coefficient (m/(L/s)²). Match the units shown beside each field and review the result together with the assumptions below.

What is a worked example of Quadratic pump system operating point?

Pump shutoff head (m) = 40; Pump head-curve coefficient (m/(L/s)²) = 0.1; System static head (m) = 10; System resistance coefficient (m/(L/s)²) = 0.2. Curve-intersection flow: 10 L/s Operating head: 30 m The two curves intersect at 10 L/s and 30 m head. This is the modeled operating point; efficiency, cavitation and motor limits are outside the calculation.