How to use this calculator
Intersect a falling quadratic pump curve with a rising static-plus-friction system curve.
- Enter Pump shutoff head (m), Pump head-curve coefficient (m/(L/s)²), System static head (m), System resistance coefficient (m/(L/s)²). Match the units shown beside each field and review the result together with the assumptions below.
- Read the worked example below to check the expected input format and result.
- Compare another scenario by changing one input at a time. Use Reset to return to the starting values.
Quadratic pump system operating point explained
The operating point is the flow where the pump head curve meets the head required by the system curve.
How the calculation works
sqrt((h0-hs)/(a+k))
Q is flow in L/s; h0 and hs are zero-flow and static head, while a and k define the pump and system curves. Hump-free quadratic approximation over the valid pump range; no efficiency, cavitation, motor, or stability assessment is performed..
Set up the calculation
h0— Pump shutoff head (m)- Pump head at zero flow on the assumed quadratic curve. It must exceed static head for a positive-flow intersection.
a— Pump head-curve coefficient (m/(L/s)²)- Coefficient a in H_pump=h0−aQ²; flow is measured in L/s, so this unit makes the head term metres.
hs— System static head (m)- Required elevation or pressure head at zero flow; it is the vertical offset of the system curve.
k— System resistance coefficient (m/(L/s)²)- Coefficient k in H_system=hs+kQ²; it represents the modeled piping resistance over the entered flow range.
Limits of this model
Hump-free quadratic approximation over the valid pump range; no efficiency, cavitation, motor, or stability assessment is performed.
Check this example
Pump shutoff head (m) = 40; Pump head-curve coefficient (m/(L/s)²) = 0.1; System static head (m) = 10; System resistance coefficient (m/(L/s)²) = 0.2.
- Curve-intersection flow: 10 L/s
- Operating head: 30 m
The two curves intersect at 10 L/s and 30 m head. This is the modeled operating point; efficiency, cavitation and motor limits are outside the calculation.
Interpreting the result
A positive intersection gives the modeled flow and head within the pump curve’s valid range; it does not establish efficiency, cavitation margin or motor suitability.
Frequently asked questions
What if static head exceeds shutoff head?
No positive-flow operating point exists in this model.
Are the coefficient units important?
Yes, both use flow in L/s.
Does it choose a pump model?
No, enter fitted curves for your candidate.
How do I use the Quadratic pump system operating point calculator?
Enter Pump shutoff head (m), Pump head-curve coefficient (m/(L/s)²), System static head (m), System resistance coefficient (m/(L/s)²). Match the units shown beside each field and review the result together with the assumptions below.
What is a worked example of Quadratic pump system operating point?
Pump shutoff head (m) = 40; Pump head-curve coefficient (m/(L/s)²) = 0.1; System static head (m) = 10; System resistance coefficient (m/(L/s)²) = 0.2. Curve-intersection flow: 10 L/s Operating head: 30 m The two curves intersect at 10 L/s and 30 m head. This is the modeled operating point; efficiency, cavitation and motor limits are outside the calculation.