How to use this calculator
Determine how direct steam injection changes air moisture and dry-bulb temperature without assuming the process is exactly isothermal.
- Enter Inlet dry-bulb temperature (°C), Inlet humidity ratio (kg/kg dry air), Dry-air mass flow (kg/s), Injected steam mass flow (kg/s), then complete the remaining labeled fields. Match the units shown beside each field and review the result together with the assumptions below.
- Read the worked example below to check the expected input format and result.
- Compare another scenario by changing one input at a time. Use Reset to return to the starting values.
Steam injection humidifier outlet state explained
A numerical walkthrough
Inlet dry-bulb temperature (°C) = 20; Inlet humidity ratio (kg/kg dry air) = 0.005; Dry-air mass flow (kg/s) = 1; Injected steam mass flow (kg/s) = 0.003; Injected steam specific enthalpy (kJ/kg) = 2676; Absolute air pressure (Pa) = 101325.
- Outlet dry-bulb temperature: 20.404945 °C
- Outlet humidity ratio: 0.008 kg/kg dry air
- Outlet moist-air enthalpy: 40.839 kJ/kg dry air
Injecting 0.003 kg/s steam at 2,676 kJ/kg into 1 kg/s dry air at 20 °C and humidity ratio 0.005 raises humidity ratio to 0.008 and dry bulb to 20.4049 °C. Added steam enthalpy changes temperature as well as water content.
The model behind the numbers
w₂=w₁+msteam/mdry; h₂=h₁+(msteam/mdry)hsteam; h=1.006T+w(2501+1.86T).
Conserve dry air, added water and total stream enthalpy. The outlet temperature follows from the moist-air enthalpy expression; both inlet and outlet are checked against water saturation.
What to enter
T— Inlet dry-bulb temperature (°C)- Inlet dry-bulb temperature (°C). Enter the value for this state; the units shown are used without an unstated conversion.
w— Inlet humidity ratio (kg/kg dry air)- Inlet humidity ratio (kg/kg dry air). Enter the value for this state; the units shown are used without an unstated conversion.
ma— Dry-air mass flow (kg/s)- Dry-air mass flow (kg/s). Enter the value for this state; the units shown are used without an unstated conversion.
ms— Injected steam mass flow (kg/s)- Injected steam mass flow (kg/s). Enter the value for this state; the units shown are used without an unstated conversion.
hs— Injected steam specific enthalpy (kJ/kg)- Injected steam specific enthalpy (kJ/kg). Enter the value for this state; the units shown are used without an unstated conversion.
p— Absolute air pressure (Pa)- Absolute air pressure (Pa). Enter the value for this state; the units shown are used without an unstated conversion.
Interpreting the result
Ideal moist air, 0–100 °C liquid-water saturation formula, no duct loss or liquid droplet carryover. Supersaturation is rejected rather than silently discarding water.
Reading the outputs
Dry-bulb temperature uses Celsius; humidity and enthalpy are per kilogram of dry air.
Frequently asked questions
Must air heat up when steam is added?
The outlet depends on injected steam enthalpy and inlet state; solve the balance rather than imposing a temperature.
Is mass flow total moist-air mass?
No. The air-flow field is dry-air mass only.
What if fog forms?
This unsaturated calculation rejects that state; liquid condensate needs its own energy balance.
How do I use the Steam injection humidifier outlet state calculator?
Enter Inlet dry-bulb temperature (°C), Inlet humidity ratio (kg/kg dry air), Dry-air mass flow (kg/s), Injected steam mass flow (kg/s), then complete the remaining labeled fields. Match the units shown beside each field and review the result together with the assumptions below.
What is a worked example of Steam injection humidifier outlet state?
Inlet dry-bulb temperature (°C) = 20; Inlet humidity ratio (kg/kg dry air) = 0.005; Dry-air mass flow (kg/s) = 1; Injected steam mass flow (kg/s) = 0.003; Injected steam specific enthalpy (kJ/kg) = 2676; Absolute air pressure (Pa) = 101325. Outlet dry-bulb temperature: 20.404945 °C Outlet humidity ratio: 0.008 kg/kg dry air Outlet moist-air enthalpy: 40.839 kJ/kg dry air Injecting 0.003 kg/s steam at 2,676 kJ/kg into 1 kg/s dry air at 20 °C and humidity ratio 0.005 raises humidity ratio to 0.008 and dry bulb to 20.4049 °C. Added steam enthalpy changes temperature as well as water content.
Background or definition reference: EnergyPlus air-system humidifier moisture and enthalpy balances.
Read our calculation methodology.