Steam injection humidifier outlet state calculator

Determine how direct steam injection changes air moisture and dry-bulb temperature without assuming the process is exactly isothermal.

4,000 tools
Steam injection humidifier outlet state calculator — Inlet dry-bulb temperature (°C), Inlet humidity ratio (kg/kg dry air), Dry-air mass flow (kg/s) and calculation method
Steam injection humidifier outlet state calculator: inputs and calculation method.

How to use this calculator

Determine how direct steam injection changes air moisture and dry-bulb temperature without assuming the process is exactly isothermal.

  1. Enter Inlet dry-bulb temperature (°C), Inlet humidity ratio (kg/kg dry air), Dry-air mass flow (kg/s), Injected steam mass flow (kg/s), then complete the remaining labeled fields. Match the units shown beside each field and review the result together with the assumptions below.
  2. Read the worked example below to check the expected input format and result.
  3. Compare another scenario by changing one input at a time. Use Reset to return to the starting values.
Calculation guide

Steam injection humidifier outlet state explained

Outlet dry-bulb temperature20.4049°C
Outlet dry-bulb temperature: 20.404945 °C in the worked scenario.

A numerical walkthrough

Inlet dry-bulb temperature (°C) = 20; Inlet humidity ratio (kg/kg dry air) = 0.005; Dry-air mass flow (kg/s) = 1; Injected steam mass flow (kg/s) = 0.003; Injected steam specific enthalpy (kJ/kg) = 2676; Absolute air pressure (Pa) = 101325.

  • Outlet dry-bulb temperature: 20.404945 °C
  • Outlet humidity ratio: 0.008 kg/kg dry air
  • Outlet moist-air enthalpy: 40.839 kJ/kg dry air

Injecting 0.003 kg/s steam at 2,676 kJ/kg into 1 kg/s dry air at 20 °C and humidity ratio 0.005 raises humidity ratio to 0.008 and dry bulb to 20.4049 °C. Added steam enthalpy changes temperature as well as water content.

The model behind the numbers

w₂=w₁+msteam/mdry; h₂=h₁+(msteam/mdry)hsteam; h=1.006T+w(2501+1.86T).

Conserve dry air, added water and total stream enthalpy. The outlet temperature follows from the moist-air enthalpy expression; both inlet and outlet are checked against water saturation.

What to enter

T — Inlet dry-bulb temperature (°C)
Inlet dry-bulb temperature (°C). Enter the value for this state; the units shown are used without an unstated conversion.
w — Inlet humidity ratio (kg/kg dry air)
Inlet humidity ratio (kg/kg dry air). Enter the value for this state; the units shown are used without an unstated conversion.
ma — Dry-air mass flow (kg/s)
Dry-air mass flow (kg/s). Enter the value for this state; the units shown are used without an unstated conversion.
ms — Injected steam mass flow (kg/s)
Injected steam mass flow (kg/s). Enter the value for this state; the units shown are used without an unstated conversion.
hs — Injected steam specific enthalpy (kJ/kg)
Injected steam specific enthalpy (kJ/kg). Enter the value for this state; the units shown are used without an unstated conversion.
p — Absolute air pressure (Pa)
Absolute air pressure (Pa). Enter the value for this state; the units shown are used without an unstated conversion.

Interpreting the result

Ideal moist air, 0–100 °C liquid-water saturation formula, no duct loss or liquid droplet carryover. Supersaturation is rejected rather than silently discarding water.

Reading the outputs

Dry-bulb temperature uses Celsius; humidity and enthalpy are per kilogram of dry air.

Frequently asked questions

Must air heat up when steam is added?

The outlet depends on injected steam enthalpy and inlet state; solve the balance rather than imposing a temperature.

Is mass flow total moist-air mass?

No. The air-flow field is dry-air mass only.

What if fog forms?

This unsaturated calculation rejects that state; liquid condensate needs its own energy balance.

How do I use the Steam injection humidifier outlet state calculator?

Enter Inlet dry-bulb temperature (°C), Inlet humidity ratio (kg/kg dry air), Dry-air mass flow (kg/s), Injected steam mass flow (kg/s), then complete the remaining labeled fields. Match the units shown beside each field and review the result together with the assumptions below.

What is a worked example of Steam injection humidifier outlet state?

Inlet dry-bulb temperature (°C) = 20; Inlet humidity ratio (kg/kg dry air) = 0.005; Dry-air mass flow (kg/s) = 1; Injected steam mass flow (kg/s) = 0.003; Injected steam specific enthalpy (kJ/kg) = 2676; Absolute air pressure (Pa) = 101325. Outlet dry-bulb temperature: 20.404945 °C Outlet humidity ratio: 0.008 kg/kg dry air Outlet moist-air enthalpy: 40.839 kJ/kg dry air Injecting 0.003 kg/s steam at 2,676 kJ/kg into 1 kg/s dry air at 20 °C and humidity ratio 0.005 raises humidity ratio to 0.008 and dry bulb to 20.4049 °C. Added steam enthalpy changes temperature as well as water content.