Use the billed peak, not a monthly average
Enter the peak demand the utility uses for the bill in kW and the matching demand rate in currency per kW. Both fields are nonnegative. A business may have used modest total energy yet created a short high-power interval; the billed maximum can still drive the demand charge under its tariff.
Demand is a rate of energy use, usually averaged over a tariff-defined interval, while kWh is energy accumulated over time. A 100 kW peak does not mean the customer used 100 kWh. Check the bill, interval-meter data, and tariff definition before choosing a value; some schedules use separate seasonal or time-window peaks.
Multiply the two tariff quantities
Demand charge = billed peak kW × demand rate ($/kW). The units cancel to currency. At 120 kW and $18.50 per kW, the modeled charge is $2,220. The calculator displays the charge and peak to two decimals, matching a readable bill estimate rather than reproducing the utility’s internal rounding or ratchet rules.
Use the billed demand for the same month and rate. Substituting a nameplate equipment rating or the highest instantaneous sample can overstate the tariff input if the utility uses a longer interval; using an average kW over the whole month can understate it. The equation is simple, but choosing the tariff-defined peak is the important data step.
Separate demand from energy charges
The demand line is generally distinct from energy charges based on kWh. A utility bill may also include fixed fees, taxes, power-factor penalties, riders, ratchets, and time-of-use demand windows. EIA defines a demand charge around maximum capacity usage under the applicable rate schedule, which is why the tariff and billing period matter.
An on-site battery or generator may reduce a peak only if it is operating during the relevant interval and the tariff recognizes the resulting meter reading. This calculator does not model load shifting, coincident peaks, demand ratchets, or the costs of controls and storage. It estimates the direct product after the applicable billed peak is known.
Compare two billed peaks
At 75 kW and $24.75/kW, the charge is $1,856.25. The rate is higher than the first example, so the smaller peak does not automatically yield the smaller bill by a fixed percentage; each scenario combines its own peak and tariff. Read the resulting line next to the relevant rate schedule.
Demand reductions can be evaluated by changing peak kW while holding the rate fixed, but that is a scenario, not a promise of savings. A tariff may use the maximum among several windows or carry forward a prior peak. Verify the bill’s billed demand rather than assuming the calculator’s one-peak input captures a multi-component schedule.
Worked examples
Commercial billed peak
Inputs: Billed peak 120 kW; demand rate $18.50/kW.
Calculation: Demand charge = 120 × 18.50 = $2,220.00.
The estimated demand-charge line is $2,220.00 before other bill components.
Lower peak on another tariff
Inputs: Billed peak 75 kW; demand rate $24.75/kW.
Calculation: Demand charge = 75 × 24.75 = $1,856.25.
The charge is $1,856.25 using this period’s billed peak and rate.
Use the estimate for a focused review
Use this calculation to reconcile one demand-charge line or estimate the dollar effect of a peak reduction. Keep the billing month, demand interval, seasonal window, and price source with the result. If the utility reports kVA rather than kW or applies a power-factor adjustment, do not enter those numbers without converting and checking the tariff’s rule.
The output excludes energy, taxes, and demand rules that are not represented by the single rate. It does not say whether a charge is avoidable or whether an alternative tariff is cheaper. Compare complete bills using actual load data and the utility’s eligible rate options before making an operating or equipment decision.