Keep the solar and battery inputs separate
The form asks for array rated power in kW, peak sun hours per day, and performance ratio from 0 to 1. It also asks for battery capacity in kWh, average load in kW, and usable fraction from 0 to 1. The solar values produce the full-load-hour and daily-generation outputs; the battery values produce the runtime. A change to battery capacity does not change the solar hours, and a change to irradiation does not alter the battery energy entered.
Rated power and average load must be positive. Sun hours and capacity may be zero; performance and usable fractions must stay within 0–1. Enter a battery usable fraction such as 0.85 for 85 percent rather than the whole number 85. Keep energy in kWh and power in kW so the time output is in hours without another conversion.
Convert the resource into full-load hours
The solar calculation multiplies peak sun hours by the performance ratio. If a site has 4.5 peak sun hours and the selected ratio is 0.80, the equivalent full-load time is 3.6 hours. Multiplying that by a 5 kW array gives an estimated 18 kWh of daily generation. The figure is an energy-equivalent duration at nameplate power, not a claim that the system runs at full output for a continuous 3.6-hour block.
The ratio keeps one simplified loss assumption visible, but it does not include every array or inverter detail individually. Orientation, irradiance sensor plane, module temperature, shade, snow, clipping, outages, and mismatch may affect output. For a location-specific forecast, use a weather-based production model; this calculator’s purpose is to convert a chosen resource assumption into transparent comparison terms.
Calculate battery runtime from usable energy
Usable battery energy is capacity multiplied by the usable fraction. Runtime is usable kWh divided by the average kW load. For a 10 kWh battery at 85 percent usable energy and a 0.7 kW average load, the estimate is 8.5 ÷ 0.7 = 12.1429 hours. This assumes the load remains steady and that usable energy is already a suitable value for the battery chemistry and operating range.
This estimate does not subtract inverter conversion losses because efficiency is not an input. Do not present it as a guaranteed UPS or backup duration. A real system may stop at a voltage threshold, derate at high current, age over time, or lose energy in an inverter and wiring. If those effects matter, adjust the usable fraction conservatively or use a model with explicit efficiency and discharge-rate inputs.
Interpret both outputs without mixing them
The primary display rounds equivalent full-load hours to four decimals and also reports estimated daily PV generation and battery runtime, each at four-decimal precision. The companion lines show rated array power, usable battery energy, and the selected performance ratio. Those inputs are usually less precise than the display.
A second scenario with 8 kW of PV, 5.1 peak sun hours, a 0.76 ratio, 16 kWh of battery capacity, a 1.2 kW load, and 0.80 usable fraction gives 3.876 full-load hours and 31.008 kWh/day. The battery estimate is 12.8 ÷ 1.2 = 10.6667 hours. The PV output is not automatically stored in the battery; charging timing and system controls are outside this arithmetic.
Worked examples
Daily solar and battery screening case
Inputs: Array 5 kW; 4.5 sun hours; PR 0.80; battery 10 kWh; average load 0.7 kW; usable fraction 0.85.
Calculation: Full-load hours = 4.5 × 0.80 = 3.6 h. PV energy = 5 × 3.6 = 18 kWh/day. Runtime = 10 × 0.85 ÷ 0.7 = 12.1429 h.
The tool displays about 3.6000 full-load hours and 12.1429 hours of idealized battery runtime.
A higher-output system with a larger steady load
Inputs: Array 8 kW; 5.1 sun hours; PR 0.76; battery 16 kWh; average load 1.2 kW; usable fraction 0.80.
Calculation: Full-load hours = 5.1 × 0.76 = 3.876 h. PV energy = 8 × 3.876 = 31.008 kWh/day. Runtime = 16 × 0.80 ÷ 1.2 = 10.6667 h.
The solar estimate and battery estimate are separate outputs; the calculator does not model charging the battery from that PV energy.
Use this as a paired screening estimate
The model does not calculate battery charge time, state-of-charge changes during solar production, inverter sizing, or load surges. It also does not check that a battery and PV array are electrically compatible. A system can have enough daily solar energy in total but still require grid power overnight because energy arrives at the wrong time or storage is limited.
Use the solar output to check an energy budget and the runtime output to screen a steady-load backup case. For design, gather hourly demand and production, battery limits, inverter efficiency, temperatures, and equipment ratings. Safety, warranty, and outage decisions need manufacturer data and a method matched to the system.