Cooling COP: Measure Cooling Delivered per Unit of Input Power

Cooling COP compares heat removed from a space with the electrical power used to remove it. The calculator divides cooling output by electrical input, both in kW, producing a unitless ratio. Use the heat pump cooling COP calculator for one measured or specified operating point, and keep the cooling conditions with the result.

Open calculator
A cooling heat pump removes heat from an indoor space while electric input drives the compressor and fans.

Share this article

Cooling output removed from an indoor space is compared with electrical input to a heat pump.
Cooling COP is useful cooling divided by electrical power.

Pair useful cooling and electrical power

Enter cooling output in kW and electric input in kW. Input power must be positive and cooling output may be zero or greater. Convert any Btu/h value to kW before entering it, and make sure output and input refer to the same time interval, compressor stage, fan boundary, and equipment configuration.

COP cooling = cooling output ÷ electrical input. Because the units match, the ratio has no units. If a system removes 8 kW of heat while using 2 kW of electric power, the calculated COP is 4. The number can exceed one because cooling equipment moves heat rather than converting electricity directly into an equal amount of cooling.

Interpret the cooling condition

Cooling output and power change as indoor and outdoor temperatures, airflow, humidity, coil cleanliness, refrigerant charge, and compressor speed change. A rating measured at a specific test condition should be compared with another rating only when test procedures and boundaries are comparable. Do not apply a mild-day point value across a hot season.

The calculator uses up to four decimal places for COP and displays the input powers to three decimals in its explanation. These display settings do not make sensor readings more accurate. Report the source of the capacities and the indoor/outdoor conditions, especially if the result is used for a retrofit comparison.

Keep cooling COP distinct from EER

COP is a unitless ratio when output and input use the same power unit. EER expresses cooling output in Btu per watt-hour; its numerical value is not identical to COP. The relationship uses a unit conversion, so a COP of 4 corresponds to an EER near 13.65 Btu/Wh under the same point boundary, not an EER of 4.

DOE guidance defines COP with the useful cooling effect and net work input in identical units, while EER uses Btu relative to electrical input. Seasonal ratings such as SEER or SEER2 add a prescribed range of conditions. Keep the metric and test method explicit instead of placing all efficiency labels on one scale.

Compare two cooling checks

At 8 kW cooling and 2 kW electric input, COP is 4.0000. At 14.4 kW cooling and 4.8 kW input, it is 3.0000. The output-to-input ratios are easy to check, but they do not say how much electricity a building will use without its cooling load profile and operating hours. If cooling capacity comes from a catalogue rather than a meter, retain the listed rating condition; a measured input at a different ambient temperature is not a matched point.

Use the same electrical boundary in numerator and denominator decisions. A system-level cooling value divided by compressor-only watts will overstate total system COP if fans and pumps consume additional power. Conversely, including auxiliary equipment on only one side makes the ratio inconsistent.

Worked examples

Steady cooling point

Inputs: Cooling output 8 kW; electrical input 2 kW.

Calculation: Cooling COP = 8 ÷ 2 = 4.

COP cooling is 4 at this point; no seasonal average is implied.

Larger cooling unit

Inputs: Cooling output 14.4 kW; electrical input 4.8 kW.

Calculation: Cooling COP = 14.4 ÷ 4.8 = 3.

The point ratio is 3; compare against matching test temperatures and equipment boundaries.

A unitless COP ratio is converted to an EER value in Btu per watt-hour using a unit conversion.
COP and EER use different units and scales.

Apply the result to a real comparison

A point COP is descriptive, not a guaranteed savings percentage. Annual cost depends on climate, run time, control settings, indoor conditions, electricity price, cycling, and maintenance. A higher COP at one rating point may not lead to a lower annual bill if the comparison conditions or cooling load differ. Cooling load can include both sensible temperature reduction and moisture removal, so use a capacity measurement that reflects the same definition as the equipment rating.

Use a manufacturer’s performance map or an accepted rating for a purchase decision, and a measured point for troubleshooting only when instrumentation and boundaries are clear. The calculator does not diagnose refrigerant charge, airflow, installation quality, or comfort. It carries out the ratio from the two inputs.