Enter cooling output and electric input
Use cooling capacity in kW and electrical input power in kW at the same operating point. Input must be positive, while cooling capacity can be zero or greater. If your source gives Btu/h or watts, convert to kW consistently before entry; avoid mixing a rated output with a measured input from a different load or test condition.
The factor 3.412 converts the kilowatt ratio to Btu per watt-hour: 1 kW of cooling is 3,412 Btu/h, and 1 kW of electric input is 1,000 W. The calculator uses this rounded conversion and reports EER to four decimal places.
Understand the units and metric
EER is commonly expressed in Btu/Wh, not as a percentage. A higher value means more cooling output per electrical watt-hour under the stated test condition. For 10.5 kW of cooling and 3.5 kW of electric input, the cooling-to-input ratio is 3, and the EER is 10.236 Btu/Wh using the calculator constant.
EER is not the same as COP, even though both describe cooling relative to input. COP is dimensionless when both quantities use the same units; EER includes the Btu-to-watt-hour factor. DOE materials define EER using cooling capacity and electrical input and distinguish it from seasonal metrics, which combine multiple test conditions. The calculator fixes the factor at 3.412, so using a more precise conversion can shift the last displayed digits without changing the metric’s interpretation.
Keep test conditions with the value
Air-conditioning performance varies with indoor and outdoor temperature, airflow, humidity, compressor speed, and included fans. A value from a rating test should be compared with another EER under matching conditions and procedures. Do not assume a rated point EER remains constant through a hot season or part-load operation.
The input contract requires positive electrical power and nonnegative cooling capacity. Output shows up to four decimal places in Btu/Wh; intermediate measurements may be rounded by their source. Keep the original input values and the equipment’s test point with the result so another person can reproduce the calculation. If one value is a catalog rating and the other comes from a field test, make the condition difference explicit instead of treating the output as a standardized rating.
Compare two point ratios
At 10.5 kW cooling and 3.5 kW electric input, EER = 3.412 × 10.5 ÷ 3.5 = 10.2360 Btu/Wh. At 7.2 kW cooling and 2.4 kW input, the same ratio produces the same EER. Equal EER values can occur at different equipment capacities because the metric normalizes cooling by input.
Those examples do not imply equal seasonal consumption. One unit might run at a different load, cycle differently, or include a different fan boundary. To estimate energy use, a separate load profile and operating schedule are needed; multiplying a test-point EER by a nameplate capacity cannot predict a bill.
Worked examples
3-to-1 cooling-to-input ratio
Inputs: Cooling output 10.5 kW; electrical input 3.5 kW.
Calculation: EER = 3.412 × 10.5 ÷ 3.5 = 10.236 Btu/Wh.
The point EER is 10.236 Btu/Wh using the calculator’s four-decimal maximum.
A smaller unit at the same point ratio
Inputs: Cooling output 7.2 kW; electrical input 2.4 kW.
Calculation: EER = 3.412 × 7.2 ÷ 2.4 = 10.236 Btu/Wh.
The same ratio gives the same 10.236 Btu/Wh EER, despite different absolute capacity.
Use EER for the right comparison
Use the calculator to reproduce an EER from matching point data or convert a cooling-to-input ratio to the customary unit. Do not compare EER directly with a dimensionless COP or with SEER/SEER2 without a rating-method context. The test basis and equipment category matter as much as the final number.
Product selection and compliance should use the applicable current rating standard and manufacturer data. The calculation does not establish an efficiency classification, savings, sizing, or performance at another temperature. If the computed value conflicts with a published value, first compare units, included power, rounding, and test conditions.