Gather ratings from the same battery
Enter rated capacity in Ah, its rating time in hours, constant load current in amperes, and the Peukert exponent k. A 100 Ah rating at 20 hours corresponds to a rated test current of 5 A. The exponent describes how the battery’s available capacity changes with discharge rate and should come from a manufacturer, a suitable test, or a validated model.
All three capacity, time, and current inputs must be positive. The accepted exponent range is 1 to 5, while practical values for many lead-acid batteries are much closer to 1. Do not choose a value merely to match a desired runtime. The exponent is empirical, and its meaning depends on the rating data and battery conditions.
Understand the adjustment
First calculate rated current Iᵣ = capacity C ÷ rating time H. Then estimate runtime t = H × (Iᵣ ÷ load current)^k. The calculator also reports estimated delivered capacity as load current × runtime. If the load current equals the rated test current, the ratio is one and the model returns the stated rating time.
For a higher load current, the ratio Iᵣ/I is below one; raising it to an exponent greater than one shortens estimated runtime more than a simple Ah ÷ A quotient. If load current is lower than the test current, the equation can estimate a longer duration. It remains an empirical approximation, not a full electrochemical model.
Choose a defensible exponent
Victron’s battery-monitor documentation explains that effective capacity depends on discharge rate and that the Peukert exponent can be configured for a particular battery. A value measured or specified for one lead-acid model should not automatically be reused for another chemistry or size. Confirm which rating period the manufacturer used, because changing H changes rated current and the reference point.
The output is most useful for a steady current and approximately stable temperature. It does not model a variable household load, voltage cutoff, aging, wiring, temperature swings, charge history, or a battery-management system. If the load changes repeatedly, a single current and exponent flatten important behavior; use measured data or a model validated for the duty cycle.
Compare two constant-current cases
At 100 Ah rated over 20 hours, the reference current is 5 A. With a 10 A load and exponent 1.2, the model estimates about 8.706 hours and about 87.06 Ah delivered. At twice the test current, the runtime is well below the simple 10-hour quotient because k exceeds one.
For 200 Ah rated at 20 hours, the reference current is 10 A. A 15 A load and exponent 1.15 produce a different adjustment. The calculator displays runtime to three decimals, delivered Ah to two, and reference current to three; retain the input exponent and rating basis so another reader can reproduce the comparison.
Worked examples
Twice the rating test current
Inputs: Rated 100 Ah over 20 h; constant load 10 A; exponent 1.20.
Calculation: Rated current = 100 ÷ 20 = 5 A; runtime = 20 × (5 ÷ 10)^1.20 ≈ 8.706 h.
The model estimates about 8.706 hours and 87.06 Ah delivered, subject to the stated lead-acid assumptions.
A larger rated battery under a moderate load
Inputs: Rated 200 Ah over 20 h; constant load 15 A; exponent 1.15.
Calculation: Rated current = 200 ÷ 20 = 10 A; runtime = 20 × (10 ÷ 15)^1.15 ≈ 12.547 h.
The model estimates about 12.547 hours and 188.20 Ah delivered; test conditions still control real performance.
Interpret the output as a scenario
Estimated delivered Ah is load current multiplied by predicted time; it is not a new nameplate capacity. If the result surprises you, first verify that capacity and rating time correspond to the same test and that the current units are correct. Then compare against the manufacturer discharge table at a similar cutoff voltage and temperature.
Use the Peukert model as a screening estimate for constant-current lead-acid applications. The calculator does not establish a safe discharge limit, warranty runtime, or remaining cycle life. For critical backup, mobility, or marine service, use the battery maker’s specifications and a qualified system design; a mathematical estimate alone cannot confirm safe use.