How to use this calculator
Estimate effective disinfectant contact time and CT from tank volume, flow, baffling factor, and residual concentration.
- Enter Effective tank volume (m³), Flow rate (m³/day), Baffling factor, Disinfectant residual (mg/L). Match the units shown beside each field and review the result together with the assumptions below.
- Read the worked example below to check the expected input format and result.
- Compare another scenario by changing one input at a time. Use Reset to return to the starting values.
How this calculation works
A tank’s volume divided by flow gives nominal detention time, but short-circuiting can make effective contact time smaller. Apply a user-supplied baffling factor to estimate T₁₀, then multiply by the disinfectant residual to calculate a screening CT value.
Inputs and units
volume— Effective tank volume (m³)- Water volume available for contact, not total shell volume if dead zones are excluded.
flow— Flow rate (m³/day)- Flow through the tank over the same operating condition.
factor— Baffling factor- User-supplied dimensionless factor from tank design guidance.
residual— Disinfectant residual (mg/L)- Residual concentration used for the screening CT product.
Formula
Nominal time (h) = 24 × volume (m³) ÷ flow (m³/day). T₁₀ = baffling factor × nominal time. CT (mg·min/L) = residual (mg/L) × T₁₀ (min).
Worked example
A 500 m³ tank at 1,000 m³/day has 12 hours nominal detention time. With a 0.5 baffling factor, T₁₀ is 360 minutes; at 1.2 mg/L residual, CT is 432 mg·min/L.
Assumptions and limits
This does not determine regulatory compliance or required CT. Applicable requirements depend on disinfectant, temperature, pH, organism, treatment process, and jurisdiction; use approved design data and regulations.
Frequently asked questions
What is the baffling factor?
It represents the relationship between effective contact time and nominal detention time; use a factor appropriate to the tank configuration.
Does this prove disinfection compliance?
No. Required CT is process- and jurisdiction-specific and must be checked against applicable requirements.
Should flow be average or peak?
Use the design flow condition required by the relevant treatment criterion, often a conservative operating case.
How do I use the Baffled tank effective contact time calculator?
Enter Effective tank volume (m³), Flow rate (m³/day), Baffling factor, Disinfectant residual (mg/L). Match the units shown beside each field and review the result together with the assumptions below.
What is a worked example of Baffled tank effective contact time?
A 500 m³ tank at 1,000 m³/day has 12 hours nominal detention time. With a 0.5 baffling factor, T₁₀ is 360 minutes; at 1.2 mg/L residual, CT is 432 mg·min/L.