Estimate round-trip voltage drop in a two-conductor DC cable from current and conductor dimensions. Enter your values below to see the result and method.

A better way to figure it out
Clear
inputs.
∑
Clear result · useful details
Free calculatorNo signup ✓

Related calculators

Browse engineering calculators →

DC cable voltage drop calculator — Load current (A), One-way cable length (m), Conductor area (mm²) and calculation method
DC cable voltage drop calculator: inputs and calculation method.

How to use this calculator

Estimate round-trip voltage drop in a two-conductor DC cable from current and conductor dimensions.

  1. Enter Load current (A), One-way cable length (m), Conductor area (mm²), Resistivity (Ω·mm²/m). Match the units shown beside each field and review the result together with the assumptions below.
  2. Read the worked example below to check the expected input format and result.
  3. Compare another scenario by changing one input at a time. Use Reset to return to the starting values.
Free calculator guide

Define the component and operating point

Use this estimate to size or check one part of a system from explicit inputs. Estimate round-trip voltage drop in a two-conductor DC cable from current and conductor dimensions.

Inputs and units

Design equation and example

ΔV = 2I L ρ ÷ A.

10 A over 20 m one-way with 2.5 mm² copper gives about 2.758 V drop.

For the stated conductor and loop, voltage drop scales with current and loop length and inversely with cross-sectional area.

Applying the result in a system

Treat this as a calculation for the stated component and operating point. Real installations can add losses, tolerances, boundary conditions, or code requirements beyond this model.

Assumptions and limitations

Uses a fixed resistivity and ignores temperature rise, connectors, and installation rules; the factor 2 includes outgoing and return conductors.

Source and method

NIST lists resistance-resistivity unit conversions; the entered resistivity still depends on conductor material and temperature. NIST Guide to the SI — Appendix B conversion factors.

Frequently asked questions

Which measurements belong in the dc cable voltage drop?

Enter Load current (A), One-way cable length (m), Conductor area (mm²), Resistivity (Ω·mm²/m). Verify that the values use the same operating condition and unit system.

What can make a real installation differ from this dc cable voltage drop estimate?

Uses a fixed resistivity and ignores temperature rise, connectors, and installation rules; the factor 2 includes outgoing and return conductors.

How does this differ from conductor resistance?

Conductor resistance describes the wire path. Voltage drop also uses load current and the round-trip path; this formula includes a factor of 2 for outgoing and return conductors.

How do I use the DC cable voltage drop calculator?

Enter Load current (A), One-way cable length (m), Conductor area (mm²), Resistivity (Ω·mm²/m). Match the units shown beside each field and review the result together with the assumptions below.

What is a worked example of DC cable voltage drop?

ΔV = 2I L ρ ÷ A. 10 A over 20 m one-way with 2.5 mm² copper gives about 2.758 V drop. For the stated conductor and loop, voltage drop scales with current and loop length and inversely with cross-sectional area.