Single-phase cable voltage drop calculator
Estimate resistive voltage drop in a two-conductor single-phase cable run. Enter your values below to see the result and method.
inputs.
Related calculators
These tools cover nearby questions while keeping this page focused on its own calculation.
How to use this calculator
Estimate resistive voltage drop in a two-conductor single-phase cable run.
- Enter Current (A), One-way cable length (m), Conductor resistivity (Ω·mm²/m), Cross-section (mm²). Match the units shown beside each field and review the result together with the assumptions below.
- Read the worked example below to check the expected input format and result.
- Compare another scenario by changing one input at a time. Use Reset to return to the starting values.
Define the component and operating point
Estimate resistive voltage drop in a two-conductor single-phase run. The factor of two accounts for the outgoing and return conductor when the entered length is one way.
Inputs and units
Use current, one-way cable length, resistivity, and conductor cross-section; the factor two accounts for the return path.
- Current (A): Load current through the conductor pair.
- One-way cable length (m): Route length in one direction; the formula includes the return conductor separately.
- Conductor resistivity (Ω·mm²/m): Material resistivity at the assumed conductor temperature.
- Cross-section (mm²): Area of one conductor, not the combined area of both conductors.
Design equation and example
ΔV = 2ILρ ÷ A
A 30 m one-way copper run carrying 10 A through 2.5 mm² conductors drops about 4.2 V.
Intermediate values are kept unrounded; the displayed result is rounded for readability.
Applying the result in a system
This is the resistive drop across the outgoing and return conductors. It omits reactance and connection effects, so it is not a complete compliance calculation.
Assumptions and limitations
Uses conductor resistance at the entered resistivity and neglects reactance, contact resistance, and temperature rise.
Frequently asked questions
Which measurements belong in the single-phase cable voltage drop?
Use one-way route length, conductor resistivity, and one conductor's cross-section; the formula includes the return path.
What can make a real installation differ from this single-phase cable voltage drop estimate?
Uses conductor resistance at the entered resistivity and neglects reactance, contact resistance, and temperature rise.
How do I use the Single-phase cable voltage drop calculator?
Enter Current (A), One-way cable length (m), Conductor resistivity (Ω·mm²/m), Cross-section (mm²). Match the units shown beside each field and review the result together with the assumptions below.
What is a worked example of Single-phase cable voltage drop?
ΔV = 2ILρ ÷ A A 30 m one-way copper run carrying 10 A through 2.5 mm² conductors drops about 4.2 V. Intermediate values are kept unrounded; the displayed result is rounded for readability.
What does the Single-phase cable voltage drop calculator calculate?
Estimate resistive voltage drop in a two-conductor single-phase cable run.
Read the calculation methodology and privacy policy.
Source: Schneider Electric Electrical Installation Guide: voltage drop in steady-load conditions. Shows the single-phase factor of two and the resistive/reactive conductor relation; this calculator explicitly uses the resistive-only simplification.