Single-phase cable voltage drop calculator

Estimate resistive voltage drop in a two-conductor single-phase cable run. Enter your values below to see the result and method.

A better way to figure it out
Clear
inputs.
∑
Clear result · useful details
Free calculatorNo signup ✓

Related calculators

These tools cover nearby questions while keeping this page focused on its own calculation.

Browse engineering calculators →

Single-phase cable voltage drop calculator — Current (A), One-way cable length (m), Conductor resistivity (Ω·mm²/m) and calculation method
Single-phase cable voltage drop calculator: inputs and calculation method.

How to use this calculator

Estimate resistive voltage drop in a two-conductor single-phase cable run.

  1. Enter Current (A), One-way cable length (m), Conductor resistivity (Ω·mm²/m), Cross-section (mm²). Match the units shown beside each field and review the result together with the assumptions below.
  2. Read the worked example below to check the expected input format and result.
  3. Compare another scenario by changing one input at a time. Use Reset to return to the starting values.
Free calculator guide

Define the component and operating point

Estimate resistive voltage drop in a two-conductor single-phase run. The factor of two accounts for the outgoing and return conductor when the entered length is one way.

Inputs and units

Use current, one-way cable length, resistivity, and conductor cross-section; the factor two accounts for the return path.

Design equation and example

ΔV = 2ILρ ÷ A

A 30 m one-way copper run carrying 10 A through 2.5 mm² conductors drops about 4.2 V.

Intermediate values are kept unrounded; the displayed result is rounded for readability.

Applying the result in a system

This is the resistive drop across the outgoing and return conductors. It omits reactance and connection effects, so it is not a complete compliance calculation.

Assumptions and limitations

Uses conductor resistance at the entered resistivity and neglects reactance, contact resistance, and temperature rise.

Frequently asked questions

Which measurements belong in the single-phase cable voltage drop?

Use one-way route length, conductor resistivity, and one conductor's cross-section; the formula includes the return path.

What can make a real installation differ from this single-phase cable voltage drop estimate?

Uses conductor resistance at the entered resistivity and neglects reactance, contact resistance, and temperature rise.

How do I use the Single-phase cable voltage drop calculator?

Enter Current (A), One-way cable length (m), Conductor resistivity (Ω·mm²/m), Cross-section (mm²). Match the units shown beside each field and review the result together with the assumptions below.

What is a worked example of Single-phase cable voltage drop?

ΔV = 2ILρ ÷ A A 30 m one-way copper run carrying 10 A through 2.5 mm² conductors drops about 4.2 V. Intermediate values are kept unrounded; the displayed result is rounded for readability.

What does the Single-phase cable voltage drop calculator calculate?

Estimate resistive voltage drop in a two-conductor single-phase cable run.