Three-phase cable voltage drop calculator
Estimate balanced three-phase resistive voltage drop from current, route length, conductor resistivity, and area. Enter your values below to see the result and method.
inputs.
Related calculators
These tools cover nearby questions while keeping this page focused on its own calculation.
How to use this calculator
Estimate balanced three-phase resistive voltage drop from current, route length, conductor resistivity, and area.
- Enter Line current (A), One-way length (m), Conductor resistivity (Ω·mm²/m), Cross-section (mm²), then complete the remaining labeled fields. Match the units shown beside each field and review the result together with the assumptions below.
- Read the worked example below to check the expected input format and result.
- Compare another scenario by changing one input at a time. Use Reset to return to the starting values.
Define the component and operating point
Use this estimate to size or check one part of a system from explicit inputs. Estimate balanced three-phase resistive voltage drop from current, route length, conductor resistivity, and area.
Inputs and units
Enter the values below for this model. RMS line current in amperes for the balanced three-phase load. One-way route length from source to load in metres; this model includes the three-phase √3 factor rather than doubling the length. Resistivity in Ω·mm²/m at the assumed conductor condition; actual resistivity rises with temperature. Conductor cross-sectional area in square millimetres; voltage drop varies inversely with this area. Real-power factor cosφ between 0 and 1; the resistive approximation omits the conductor-reactance term.
- Line current (A): RMS line current in amperes for the balanced three-phase load.
- One-way length (m): One-way route length from source to load in metres; this model includes the three-phase √3 factor rather than doubling the length.
- Conductor resistivity (Ω·mm²/m): Resistivity in Ω·mm²/m at the assumed conductor condition; actual resistivity rises with temperature.
- Cross-section (mm²): Conductor cross-sectional area in square millimetres; voltage drop varies inversely with this area.
- Power factor: Real-power factor cosφ between 0 and 1; the resistive approximation omits the conductor-reactance term.
Design equation and example
ΔV = √3 I L ρ PF ÷ A
A 50 m run at 20 A, 6 mm² copper, and PF 0.90 drops about 4.55 V.
Intermediate values are kept unrounded; the displayed result is rounded for readability.
Applying the result in a system
The estimate uses the entered current and conductor path; judge allowable drop using the project supply, conductor temperature, and installation conditions. Real installations can add losses, tolerances, boundary conditions, or code requirements beyond this model.
Assumptions and limitations
Resistive approximation for a balanced line; cable reactance, conductor temperature, and installation rules are excluded.
Frequently asked questions
Why does the balanced three-phase estimate include √3 and power factor?
ΔV = √3 I L ρ PF ÷ A A 50 m run at 20 A, 6 mm² copper, and PF 0.90 drops about 4.55 V.
What can make a real installation differ from this three-phase cable voltage drop estimate?
Resistive approximation for a balanced line; cable reactance, conductor temperature, and installation rules are excluded.
How do I use the Three-phase cable voltage drop calculator?
Enter Line current (A), One-way length (m), Conductor resistivity (Ω·mm²/m), Cross-section (mm²), then complete the remaining labeled fields. Match the units shown beside each field and review the result together with the assumptions below.
What is a worked example of Three-phase cable voltage drop?
ΔV = √3 I L ρ PF ÷ A A 50 m run at 20 A, 6 mm² copper, and PF 0.90 drops about 4.55 V. Intermediate values are kept unrounded; the displayed result is rounded for readability.
What does the Three-phase cable voltage drop calculator calculate?
Estimate balanced three-phase resistive voltage drop from current, route length, conductor resistivity, and area.
Read the calculation methodology and privacy policy.
Source: Electrical Installation Guide: steady-load voltage drop.