Power factor correction capacitance calculator

Estimate single-phase shunt capacitance for a target reactive power at a chosen AC frequency and voltage. Enter your values below to see the result and method.

A better way to figure it out
Clear
inputs.
∑
Clear result · useful details
Free calculatorNo signup ✓

Related calculators

These tools cover nearby questions while keeping this page focused on its own calculation.

Browse engineering calculators →

Power factor correction capacitance calculator — Reactive power to compensate (var), Frequency (Hz), RMS voltage (V) and calculation method
Power factor correction capacitance calculator: inputs and calculation method.

How to use this calculator

Estimate single-phase shunt capacitance for a target reactive power at a chosen AC frequency and voltage.

  1. Enter Reactive power to compensate (var), Frequency (Hz), RMS voltage (V). Match the units shown beside each field and review the result together with the assumptions below.
  2. Read the worked example below to check the expected input format and result.
  3. Compare another scenario by changing one input at a time. Use Reset to return to the starting values.
Free calculator guide

Define the component and operating point

This estimates an ideal single-phase shunt capacitor from reactive vars, frequency, and RMS voltage. Three-phase bank connections and harmonics require separate engineering design. Estimate single-phase shunt capacitance for a target reactive power at a chosen AC frequency and voltage.

∑
Original CalcWorldHub illustration for this calculation.

Inputs and units

Use the units printed beside each field. These values are Reactive power to compensate (var), Frequency (Hz), RMS voltage (V).

Design equation and example

C = Q ÷ (2πfV²)

1 kvar at 60 Hz and 240 V requires about 46.0 μF ideal capacitance.

Intermediate values are kept unrounded; the displayed result is rounded for readability.

Applying the result in a system

This estimates an ideal single-phase shunt capacitor from reactive vars, frequency, and RMS voltage. Three-phase bank connections and harmonics require separate engineering design.

Assumptions and limitations

Single-phase ideal-capacitor estimate; three-phase bank connections, voltage rating, harmonics, and switching transients need separate design.

Frequently asked questions

Which measurements belong in the power factor correction capacitance?

Enter Reactive power to compensate (var), Frequency (Hz), RMS voltage (V). Verify that the values use the same operating condition and unit system.

What can make a real installation differ from this power factor correction capacitance estimate?

Single-phase ideal-capacitor estimate; three-phase bank connections, voltage rating, harmonics, and switching transients need separate design.

How do I use the Power factor correction capacitance calculator?

Enter Reactive power to compensate (var), Frequency (Hz), RMS voltage (V). Match the units shown beside each field and review the result together with the assumptions below.

What is a worked example of Power factor correction capacitance?

C = Q ÷ (2πfV²) 1 kvar at 60 Hz and 240 V requires about 46.0 μF ideal capacitance. Intermediate values are kept unrounded; the displayed result is rounded for readability.

What does the Power factor correction capacitance calculator calculate?

Estimate single-phase shunt capacitance for a target reactive power at a chosen AC frequency and voltage.