How to use this calculator
Split throttled refrigerant into vapor injection and evaporator liquid in an adiabatic intermediate-pressure flash economizer.
- Enter High-pressure liquid inlet enthalpy (kJ/kg), Intermediate saturated-liquid enthalpy (kJ/kg), Intermediate saturated-vapor enthalpy (kJ/kg), Flow entering flash separator (kg/s). Match the units shown beside each field and review the result together with the assumptions below.
- Read the worked example below to check the expected input format and result.
- Compare another scenario by changing one input at a time. Use Reset to return to the starting values.
Refrigeration flash economizer separator split explained
Use inlet and intermediate-pressure saturated enthalpies to estimate the vapor fraction produced by throttling into a flash economizer.
How the calculation works
y=(hin−hf,int)/(hg,int−hf,int); mv=y min; ml=(1−y)min.
Use the same refrigerant enthalpy reference for feed and intermediate saturated phases. Unlike a composition flash calculation, the energy balance of a single pure fluid sets vapor mass fraction.
Set up the calculation
hin— High-pressure liquid inlet enthalpy (kJ/kg)- Specific enthalpy of the high-pressure liquid entering the throttling valve.
hf— Intermediate saturated-liquid enthalpy (kJ/kg)- Saturated-liquid enthalpy at the intermediate flash pressure.
hg— Intermediate saturated-vapor enthalpy (kJ/kg)- Saturated-vapor enthalpy at that same intermediate pressure; it must exceed hf.
md— Flow entering flash separator (kg/s)- Total mass flow entering the flash separator before it splits into liquid and vapor.
Limits of this model
Pure fluid at known equilibrium separator pressure, negligible heat leak, no entrained droplets or pressure-loss model.
Check this example
High-pressure liquid inlet enthalpy (kJ/kg) = 260; Intermediate saturated-liquid enthalpy (kJ/kg) = 220; Intermediate saturated-vapor enthalpy (kJ/kg) = 410; Flow entering flash separator (kg/s) = 0.5.
- Flash vapor fraction: 21.052632 %
- Vapor injection mass flow: 0.105263 kg/s
- Liquid to evaporator: 0.394737 kg/s
A 0.5 kg/s stream throttles to a separator where hf=220 and hg=410 kJ/kg while its inlet enthalpy is 260 kJ/kg. The flash vapor fraction is 21.0526%, splitting the flow into 0.105263 kg/s vapor and 0.394737 kg/s liquid.
Reading the outputs
Vapor percent is mass-based; the two outlet flows sum to inlet flow.
Frequently asked questions
Is the vapor fraction based on moles?
No. This energy-based separator split uses mass.
Can all incoming fluid remain liquid?
Yes. Feed enthalpy equal to saturated-liquid enthalpy gives zero flash vapor.
Does this calculate the intermediate pressure optimum?
No. Supply saturation enthalpies at a chosen pressure and compare alternatives.
How do I use the Refrigeration flash economizer separator split calculator?
Enter High-pressure liquid inlet enthalpy (kJ/kg), Intermediate saturated-liquid enthalpy (kJ/kg), Intermediate saturated-vapor enthalpy (kJ/kg), Flow entering flash separator (kg/s). Match the units shown beside each field and review the result together with the assumptions below.
What is a worked example of Refrigeration flash economizer separator split?
High-pressure liquid inlet enthalpy (kJ/kg) = 260; Intermediate saturated-liquid enthalpy (kJ/kg) = 220; Intermediate saturated-vapor enthalpy (kJ/kg) = 410; Flow entering flash separator (kg/s) = 0.5. Flash vapor fraction: 21.052632 % Vapor injection mass flow: 0.105263 kg/s Liquid to evaporator: 0.394737 kg/s A 0.5 kg/s stream throttles to a separator where hf=220 and hg=410 kJ/kg while its inlet enthalpy is 260 kJ/kg. The flash vapor fraction is 21.0526%, splitting the flow into 0.105263 kg/s vapor and 0.394737 kg/s liquid.