Vapor compression refrigeration state balance calculator

Calculate the refrigeration effect, compressor demand and condenser load of a four-state vapor-compression system.

4,000 tools
Vapor compression refrigeration state balance calculator — Compressor inlet enthalpy (kJ/kg), Compressor discharge enthalpy (kJ/kg), Condenser liquid exit enthalpy (kJ/kg) and calculation method
Vapor compression refrigeration state balance calculator: inputs and calculation method.

How to use this calculator

Calculate the refrigeration effect, compressor demand and condenser load of a four-state vapor-compression system.

  1. Enter Compressor inlet enthalpy (kJ/kg), Compressor discharge enthalpy (kJ/kg), Condenser liquid exit enthalpy (kJ/kg), Refrigerant mass flow (kg/s). Match the units shown beside each field and review the result together with the assumptions below.
  2. Read the worked example below to check the expected input format and result.
  3. Compare another scenario by changing one input at a time. Use Reset to return to the starting values.
Calculation guide

Vapor compression refrigeration state balance explained

Cooling COP3
Cooling COP: 3 in the worked scenario.

A numerical walkthrough

Compressor inlet enthalpy (kJ/kg) = 400; Compressor discharge enthalpy (kJ/kg) = 450; Condenser liquid exit enthalpy (kJ/kg) = 250; Refrigerant mass flow (kg/s) = 0.05.

  • Cooling COP: 3
  • Evaporator duty: 7.5 kW
  • Compressor power: 2.5 kW
  • Condenser duty: 10 kW

A 0.05 kg/s refrigerant stream has h1=400, h2=450 and h3=h4=250 kJ/kg. It absorbs 7.5 kW, requires 2.5 kW compressor power and rejects 10 kW, giving cooling COP 3.

The model behind the numbers

h₄=h₃ for throttling; qL=h₁−h₄; w=h₂−h₁; qH=h₂−h₃; COP=qL/w.

The expansion valve is isenthalpic, so its outlet enthalpy equals condenser-liquid enthalpy. Actual compressor discharge enthalpy already includes compressor inefficiency.

What to enter

h1 — Compressor inlet enthalpy (kJ/kg)
Compressor inlet enthalpy (kJ/kg). Enter the value for this state; the units shown are used without an unstated conversion.
h2 — Compressor discharge enthalpy (kJ/kg)
Compressor discharge enthalpy (kJ/kg). Enter the value for this state; the units shown are used without an unstated conversion.
h3 — Condenser liquid exit enthalpy (kJ/kg)
Condenser liquid exit enthalpy (kJ/kg). Enter the value for this state; the units shown are used without an unstated conversion.
md — Refrigerant mass flow (kg/s)
Refrigerant mass flow (kg/s). Enter the value for this state; the units shown are used without an unstated conversion.

Interpreting the result

No refrigerant property database, suction pressure drop, motor loss or condenser fan power. All enthalpies must use one reference convention.

Reading the outputs

COP is dimensionless; all three duties are kW for the supplied refrigerant mass flow.

Frequently asked questions

Can this compare refrigerants?

Only after obtaining consistent state enthalpies for each refrigerant and operating condition.

Should expansion-valve work be subtracted?

No useful shaft work is recovered by the ideal throttling valve.

Why is condenser duty larger than cooling duty?

It rejects evaporator heat plus compressor work.

How do I use the Vapor compression refrigeration state balance calculator?

Enter Compressor inlet enthalpy (kJ/kg), Compressor discharge enthalpy (kJ/kg), Condenser liquid exit enthalpy (kJ/kg), Refrigerant mass flow (kg/s). Match the units shown beside each field and review the result together with the assumptions below.

What is a worked example of Vapor compression refrigeration state balance?

Compressor inlet enthalpy (kJ/kg) = 400; Compressor discharge enthalpy (kJ/kg) = 450; Condenser liquid exit enthalpy (kJ/kg) = 250; Refrigerant mass flow (kg/s) = 0.05. Cooling COP: 3 Evaporator duty: 7.5 kW Compressor power: 2.5 kW Condenser duty: 10 kW A 0.05 kg/s refrigerant stream has h1=400, h2=450 and h3=h4=250 kJ/kg. It absorbs 7.5 kW, requires 2.5 kW compressor power and rejects 10 kW, giving cooling COP 3.