How to use this calculator
Separate useful Peltier cooling from Joule heating and parasitic conduction for a complete thermoelectric module.
- Enter Whole-module Seebeck coefficient (V/K), Whole-module electrical resistance (ohm), Whole-module thermal conductance (W/K), Applied current in cooling direction (A), then complete the remaining labeled fields. Match the units shown beside each field and review the result together with the assumptions below.
- Read the worked example below to check the expected input format and result.
- Compare another scenario by changing one input at a time. Use Reset to return to the starting values.
Thermoelectric module cooling and hot-side rejection explained
How the calculation works
Qc=SITc−I²R/2−K(Th−Tc); P=I[S(Th−Tc)+IR]; Qh=Qc+P; COP=Qc/P.
Use whole-module properties at the operating temperature. Half of distributed Joule heat is assigned to each face in the constant-property model; the electrical input also includes the Seebeck voltage.
Set up the calculation
S— Whole-module Seebeck coefficient (V/K)- Whole-module Seebeck coefficient (V/K). Enter the value for this state; the units shown are used without an unstated conversion.
R— Whole-module electrical resistance (ohm)- Whole-module electrical resistance (ohm). Enter the value for this state; the units shown are used without an unstated conversion.
K— Whole-module thermal conductance (W/K)- Whole-module thermal conductance (W/K). Enter the value for this state; the units shown are used without an unstated conversion.
I— Applied current in cooling direction (A)- Applied current in cooling direction (A). Enter the value for this state; the units shown are used without an unstated conversion.
Tc— Cold face temperature (K)- Cold face temperature (K). Enter the value for this state; the units shown are used without an unstated conversion.
Th— Hot face temperature (K)- Hot face temperature (K). Enter the value for this state; the units shown are used without an unstated conversion.
Limits of this model
Constant module properties, uniform face temperatures, negligible Thomson heat and contact losses. Does not solve heatsink temperatures or certify manufacturer performance.
Check this example
Whole-module Seebeck coefficient (V/K) = 0.05; Whole-module electrical resistance (ohm) = 2; Whole-module thermal conductance (W/K) = 0.8; Applied current in cooling direction (A) = 3; Cold face temperature (K) = 280; Hot face temperature (K) = 310.
- Cold-side net heat absorption: 9 W
- Hot-side total heat rejection: 31.5 W
- Electrical input power: 22.5 W
- Signed cooling coefficient of performance: 0.4
At 3 A, a module with S=0.05 V/K, R=2 ohm and K=0.8 W/K between 280 and 310 K absorbs only 9 W from its cold face. Electrical input is 22.5 W, so its hot-side sink must reject 31.5 W and cooling COP is 0.4.
Reading the outputs
Cold-side absorption, hot-side rejection and electrical input are W; signed COP is dimensionless. A negative Qc means the chosen operating point heats the nominal cold face.
Frequently asked questions
Should I enter one-leg or whole-module properties?
Whole-module Seebeck coefficient, resistance and conductance are required; leg properties must first be combined consistently.
Why can too much current reduce cooling?
Peltier heat scales with current while Joule heating scales with current squared.
Is hot-side load just the cooling load?
No. The heatsink must reject cooling load plus electrical input power.
How do I use the Thermoelectric module cooling and hot-side rejection calculator?
Enter Whole-module Seebeck coefficient (V/K), Whole-module electrical resistance (ohm), Whole-module thermal conductance (W/K), Applied current in cooling direction (A), then complete the remaining labeled fields. Match the units shown beside each field and review the result together with the assumptions below.
What is a worked example of Thermoelectric module cooling and hot-side rejection?
Whole-module Seebeck coefficient (V/K) = 0.05; Whole-module electrical resistance (ohm) = 2; Whole-module thermal conductance (W/K) = 0.8; Applied current in cooling direction (A) = 3; Cold face temperature (K) = 280; Hot face temperature (K) = 310. Cold-side net heat absorption: 9 W Hot-side total heat rejection: 31.5 W Electrical input power: 22.5 W Signed cooling coefficient of performance: 0.4 At 3 A, a module with S=0.05 V/K, R=2 ohm and K=0.8 W/K between 280 and 310 K absorbs only 9 W from its cold face. Electrical input is 22.5 W, so its hot-side sink must reject 31.5 W and cooling COP is 0.4.
Background or definition reference: Thermoelectric cooler energy-balance experimental study.
Read our calculation methodology.