Ventilation airflow from ACH calculator
Convert a target air-change rate and room volume into volumetric airflow.
Calculator
How to use this calculator
Convert a target air-change rate and room volume into volumetric airflow.
- Enter Room volume (m³), Target air changes per hour. Match the units shown beside each field and review the result together with the assumptions below.
- Read the worked example below to check the expected input format and result.
- Compare another scenario by changing one input at a time. Use Reset to return to the starting values.
Ventilation airflow from ACH calculator
Convert a target air-change rate and room volume into volumetric airflow.
Inputs and units
- Room volume (m³): Enclosed room volume in m³; ACH multiplied by this volume gives m³ per hour.
- Target air changes per hour: Target replacement volume per hour as a multiple of room volume; 5 ACH means five room volumes each hour.
Formula and method
Q = V·ACH/3600
Worked example
A 120 m³ room at 5 air changes per hour needs 120×5/3600≈0.1667 m³/s.
Interpreting the result
This is the ideal supply/exhaust flow implied by a well-mixed volume model, not a code-compliance determination.
Assumptions and limits
Room volume must be positive and ACH nonnegative. Actual delivered ventilation depends on mixing, leakage, occupancy, and system balancing.
Sources and method
- Relates airflow heat removal to air density, specific heat, airflow, and temperature difference; ACH conversion is volume balance per hour. U.S. Department of Energy handbook: ventilation airflow and heat load
Frequently asked questions
Which inputs determine this result?
The visible inputs are Room volume (m³), Target air changes per hour. Each is used by the displayed formula; the calculator does not use any other hidden measurement.
When does this method apply?
Room volume must be positive and ACH nonnegative. Actual delivered ventilation depends on mixing, leakage, occupancy, and system balancing.
How do I use the Ventilation airflow from ACH calculator?
Enter Room volume (m³), Target air changes per hour. Match the units shown beside each field and review the result together with the assumptions below.
What is a worked example of Ventilation airflow from ACH?
A 120 m³ room at 5 air changes per hour needs 120×5/3600≈0.1667 m³/s.