Vesic strip footing ultimate bearing capacity calculator

Estimate a long strip footing’s ideal ultimate pressure while making the selected bearing-factor convention explicit.

4,000 tools
Vesic strip footing ultimate bearing capacity calculator — Strip footing width (m), Embedment depth (m), Effective unit weight (kN/m³) and calculation method
Vesic strip footing ultimate bearing capacity calculator: inputs and calculation method.

How to use this calculator

Estimate a long strip footing’s ideal ultimate pressure while making the selected bearing-factor convention explicit.

  1. Enter Strip footing width (m), Embedment depth (m), Effective unit weight (kN/m³), Cohesion (kPa), then complete the remaining labeled fields. Match the units shown beside each field and review the result together with the assumptions below.
  2. Read the worked example below to check the expected input format and result.
  3. Compare another scenario by changing one input at a time. Use Reset to return to the starting values.
Calculation guide

Vesic strip footing ultimate bearing capacity explained

This model estimates gross ultimate pressure for a centrally loaded strip footing on level, homogeneous soil. It uses Vesic bearing-capacity factors and omits shape, inclination, groundwater, settlement, and design-factor adjustments.

Gross ultimate pressure823.894kPa
Gross ultimate pressure: 823.894005 kPa in the worked scenario.

Inputs, symbols, and units

B — Strip footing width (m)
Width of a long strip footing; plane-strain geometry is assumed.
D — Embedment depth (m)
Depth producing the uniform surcharge γD in this simplified equation.
g — Effective unit weight (kN/m³)
Consistent effective unit weight for surcharge and the soil-weight term; groundwater corrections must be chosen externally.
c — Cohesion (kPa)
Cohesion intercept of the chosen strength model.
phi — Friction angle (degrees)
Friction angle for the stated Vesic factor convention; zero friction uses the finite Nc limit.

Formula and method

qult=cNc+γDNq+0.5γBNγ; Nq=e^(πtanφ)tan²(45°+φ/2), Nc=(Nq−1)/tanφ, Nγ=2(Nq+1)tanφ.

The finite φ=0 limit is Nc=π+2. No factor of safety or load/resistance factor is silently applied, and the result is gross ultimate pressure.

A worked scenario

Strip footing width (m) = 2; Embedment depth (m) = 1; Effective unit weight (kN/m³) = 18; Cohesion (kPa) = 10; Friction angle (degrees) = 28.

  • Gross ultimate pressure: 823.894005 kPa
  • Nc: 25.803343
  • Nq: 14.719881
  • Nγ (Vesic): 16.716818

A 2 m strip footing embedded 1 m in γ=18 kN/m³ soil uses c=10 kPa and φ=28°. The three contributions are cohesion, surcharge and soil self-weight.

Assumptions and edge cases

Vertical centered load, level ground, homogeneous soil and strip geometry. No shape, depth, inclination, layering, settlement, seismic or local-shear corrections. Educational model; this is not a code-compliant design check.

Reading the outputs

Ultimate pressure is kPa; Nc, Nq and Nγ are dimensionless factors under the stated convention.

Frequently asked questions

Is this an allowable bearing pressure?

No. It is an ideal gross ultimate pressure before any design factors or settlement limit.

Why might another reference give a different Nγ?

Several bearing-capacity formulations use different Nγ expressions. This page states Vesic explicitly.

Can a square footing use these results unchanged?

No. Three-dimensional shape effects are excluded from this strip model.

How do I use the Vesic strip footing ultimate bearing capacity calculator?

Enter Strip footing width (m), Embedment depth (m), Effective unit weight (kN/m³), Cohesion (kPa), then complete the remaining labeled fields. Match the units shown beside each field and review the result together with the assumptions below.

What is a worked example of Vesic strip footing ultimate bearing capacity?

Strip footing width (m) = 2; Embedment depth (m) = 1; Effective unit weight (kN/m³) = 18; Cohesion (kPa) = 10; Friction angle (degrees) = 28. Gross ultimate pressure: 823.894005 kPa Nc: 25.803343 Nq: 14.719881 Nγ (Vesic): 16.716818 A 2 m strip footing embedded 1 m in γ=18 kN/m³ soil uses c=10 kPa and φ=28°. The three contributions are cohesion, surcharge and soil self-weight.