How to use this calculator
Determine whether a strip footing remains fully compressed and calculate the triangular contact zone after the resultant leaves the middle third.
- Enter Vertical force per unit length (kN/m), Base moment per unit length (kN m/m), Base width (m). Match the units shown beside each field and review the result together with the assumptions below.
- Read the worked example below to check the expected input format and result.
- Compare another scenario by changing one input at a time. Use Reset to return to the starting values.
Eccentric strip footing contact pressure and uplift explained
Model one-axis eccentric loading with a compression-only contact block and no tensile soil support.
How the calculation works
e=|M/N|; full contact qmax,min=N/B(1±6e/B). For B/6<e<B/2, compressed width b=3(B/2−e), qmax=2N/b.
The soil carries compression only. The model switches continuously from a trapezoid to a triangle at e=B/6 rather than reporting an artificial tensile soil pressure.
Set up the calculation
N— Vertical force per unit length (kN/m)- Compressive resultant per metre of strip footing.
M— Base moment per unit length (kN m/m)- Signed moment about the footing centre; its magnitude determines the eccentricity.
B— Base width (m)- Width in the direction over which the moment varies pressure.
Limits of this model
Rigid strip footing, one-axis eccentricity, linear compressive contact diagram and no tensile support. Foundation flexibility and biaxial loading are not represented. Educational model; this is not a code-compliant design check.
Check this example
Vertical force per unit length (kN/m) = 200; Base moment per unit length (kN m/m) = 80; Base width (m) = 2.
- Maximum contact pressure: 222.222222 kPa
- Minimum contact pressure: 0 kPa
- Compressed base width: 1.8 m
- Resultant eccentricity: 0.4 m
A 2 m base carrying 200 kN/m and 80 kN m/m has eccentricity 0.4 m, beyond the 0.333 m kern limit; the compressed width becomes 1.8 m.
Eccentricity is 0.4 m, beyond the kern limit B/6=0.333 m; partial contact gives 1.8 m compressed width, qmax≈222.22 kPa and qmin=0.
Reading the outputs
Contact pressures are kPa; compressed width and eccentricity are m. The minimum is zero once partial contact occurs.
Frequently asked questions
Does negative moment change the peak magnitude?
No. It changes which edge is most compressed; this calculator reports magnitudes.
What if e reaches half the width?
There is no finite compression-only contact width, so the input is rejected.
Is compressed width the effective-area method width?
No. This triangular contact width is not the separate B−2e effective-width bearing-capacity convention.
How do I use the Eccentric strip footing contact pressure and uplift calculator?
Enter Vertical force per unit length (kN/m), Base moment per unit length (kN m/m), Base width (m). Match the units shown beside each field and review the result together with the assumptions below.
What is a worked example of Eccentric strip footing contact pressure and uplift?
Vertical force per unit length (kN/m) = 200; Base moment per unit length (kN m/m) = 80; Base width (m) = 2. Maximum contact pressure: 222.222222 kPa Minimum contact pressure: 0 kPa Compressed base width: 1.8 m Resultant eccentricity: 0.4 m A 2 m base carrying 200 kN/m and 80 kN m/m has eccentricity 0.4 m, beyond the 0.333 m kern limit; the compressed width becomes 1.8 m. Eccentricity is 0.4 m, beyond the kern limit B/6=0.333 m; partial contact gives 1.8 m compressed width, qmax≈222.22 kPa and qmin=0.
Background or definition reference: FHWA Soils and Foundations Reference Manual, Volume II.
Reference access note: The linked FHWA Volume II PDF was not retrievable in this review. The pressure equations and example were independently checked; confirm soil-contact assumptions and the applicable bearing method before design use.