How to use this calculator
Estimate steady-state boiler blowdown flow from steam output and feedwater-to-boiler-water dissolved-solids concentrations.
- Enter Steam generation rate (lb/h), Feedwater TDS (mg/L), Boiler-water TDS (mg/L). Match the units shown beside each field and review the result together with the assumptions below.
- Read the worked example below to check the expected input format and result.
- Compare another scenario by changing one input at a time. Use Reset to return to the starting values.
How this calculation works
A boiler loses dissolved solids mainly through blowdown while steam carries away water. Under a steady-state mass balance with negligible solids carried in the steam, the boiler TDS concentration fixes the blowdown share of feedwater. This page reports the flow required for the entered steam output and measured TDS values; it does not set a safe boiler-water limit.
Inputs and units
steamRate— Steam generation rate (lb/h)- Steam leaving the boiler per hour; use the same time basis as any reported flow rate.
feedwaterTds— Feedwater TDS (mg/L)- Dissolved-solids concentration in the boiler feedwater entering the system.
boilerTds— Boiler-water TDS (mg/L)- Target or measured dissolved-solids concentration in well-mixed boiler water and continuous blowdown.
Formula
Blowdown fraction of feedwater = feedwater TDS ÷ boiler-water TDS. Blowdown flow = steam flow × feedwater TDS ÷ (boiler-water TDS − feedwater TDS).
Method
Assume continuous blowdown, steady flow and chemistry, equal concentration units, and negligible dissolved-solids carryover with steam. Solve the dissolved-solids mass balance together with feedwater = steam + blowdown.
Worked example
For 100,000 lb/h of steam, feedwater at 250 mg/L TDS and boiler water at 4,000 mg/L, the estimated blowdown is 6,666.67 lb/h, or 6.25% of feedwater. Required feedwater flow is 106,666.67 lb/h including the blowdown stream.
Assumptions and limits
Use a qualified water-treatment program to choose allowable boiler-water chemistry. This estimate excludes intermittent bottom blowdown, sludge, leakage, and solids carryover. Feedwater TDS must be below boiler-water TDS.
Frequently asked questions
Why does the calculation compare two TDS values?
At steady state, dissolved solids entering with feedwater must leave through blowdown when steam carries negligible solids.
Can this set the boiler's TDS limit?
No. Follow the boiler manufacturer and water-treatment specialist for pressure- and chemistry-specific limits.
Does this apply to bottom blowdown?
The estimate describes continuous steady blowdown; intermittent bottom blowdown needs a separate time-averaged mass balance.
How do I use the Boiler Blowdown Rate from TDS Calculator?
Enter Steam generation rate (lb/h), Feedwater TDS (mg/L), Boiler-water TDS (mg/L). Match the units shown beside each field and review the result together with the assumptions below.
What is a worked example of Boiler Blowdown Rate from TDS?
For 100,000 lb/h of steam, feedwater at 250 mg/L TDS and boiler water at 4,000 mg/L, the estimated blowdown is 6,666.67 lb/h, or 6.25% of feedwater. Required feedwater flow is 106,666.67 lb/h including the blowdown stream.
Reference: U.S. DOE steam-system guide to boiler blowdown concentration ratio and flow mass balance. See our calculation methodology.