How to use this calculator
Estimate conductor adiabatic short-circuit current withstand from conductor factor, cross-section, and clearing time.
- Enter Adiabatic conductor factor, k (A·√s/mm²), Conductor cross-sectional area (mm²), Fault-clearing time (s). Match the units shown beside each field and review the result together with the assumptions below.
- Read the worked example below to check the expected input format and result.
- Compare another scenario by changing one input at a time. Use Reset to return to the starting values.
How this calculation works
Enter the conductor-specific k factor, conductor cross-section, and fault-clearing duration. The result uses the adiabatic short-circuit relation and reports current in amperes and kiloamperes.
Inputs and units
kFactor— Adiabatic conductor factor, k (A·√s/mm²)- Select a k value that matches conductor material, insulation, and permitted temperature limits.
conductorAreaMm2— Conductor cross-sectional area (mm²)- Copper or other conductor area used by the selected k factor.
clearingTimeSeconds— Fault-clearing time (s)- Adiabatic fault duration, limited here to 5 seconds.
Formula
I = kS/√t, rearranged from S = I√t/k, for an adiabatic conductor short-circuit check.
Method
Multiply the selected material-and-insulation factor k by conductor area S, then divide by the square root of fault duration t. k must use A·√s/mm² when area is in mm² and time in seconds.
Worked example
For k = 115 A·√s/mm², a 16 mm² conductor and 0.20 s clearing time give an adiabatic current estimate of 4.114 kA.
Assumptions and limits
IEC 60364 adiabatic checks are used for short-circuit durations up to 5 s. The k factor depends on conductor material, insulation, and initial/final temperature. This estimate does not select protective devices or replace installation-code verification.
Frequently asked questions
What determines k?
The k factor depends on conductor material, insulation, and the selected initial and final conductor temperatures.
Can I use this to select a breaker?
No. Protective-device selection and fault coordination require additional installation data and applicable code checks.
Why is duration capped at 5 seconds?
The referenced adiabatic check is intended for short-circuit durations up to 5 seconds.
How do I use the Cable Adiabatic Short-Circuit Current Estimate Calculator?
Enter Adiabatic conductor factor, k (A·√s/mm²), Conductor cross-sectional area (mm²), Fault-clearing time (s). Match the units shown beside each field and review the result together with the assumptions below.
What is a worked example of Cable Adiabatic Short-Circuit Current Estimate?
For k = 115 A·√s/mm², a 16 mm² conductor and 0.20 s clearing time give an adiabatic current estimate of 4.114 kA.
Reference: IEC 60364-5-54 low-voltage installation conductor protection standard. See our calculation methodology.