CalcWorldHub
Free online calculator · no signup

Two-Wire DC Cable Voltage Drop Calculator

Estimate voltage lost and cable heating in a two-conductor DC run from current, one-way distance, conductor area, and resistivity.

4,000 tools
Two-Wire DC Cable Voltage Drop Calculator — Source voltage (V), Load current (A), One-way cable length (m) and calculation method
Two-Wire DC Cable Voltage Drop Calculator: inputs and calculation method.

How to use this calculator

Estimate voltage lost and cable heating in a two-conductor DC run from current, one-way distance, conductor area, and resistivity.

  1. Enter Source voltage (V), Load current (A), One-way cable length (m), Conductor cross-sectional area (mm²), then complete the remaining labeled fields. Match the units shown beside each field and review the result together with the assumptions below.
  2. Read the worked example below to check the expected input format and result.
  3. Compare another scenario by changing one input at a time. Use Reset to return to the starting values.
Electronics calculation

How this calculation works

A DC load current travels to the device and returns to the source, so both conductors contribute resistance. This calculator doubles the entered one-way run length, estimates loop resistance, then reports load voltage and resistive loss.

Inputs and units

supplyV — Source voltage (V)
Voltage at the source before the cable drop.
currentA — Load current (A)
Steady current through both conductors.
oneWayLengthM — One-way cable length (m)
Distance from source to load; the formula includes the return conductor.
areaMm2 — Conductor cross-sectional area (mm²)
Area of each conductor, not the combined area of the pair.
resistivity — Conductor resistivity (Ω·mm²/m)
Copper is about 0.01724 at 20°C; change this value if your conductor or temperature basis differs.

Formula

Displayed formula

Rloop = 2Lρ/A. Voltage drop ΔV = I·Rloop. Drop (%) = 100·ΔV/Vsource. Cable loss = I²·Rloop.

Method

Enter one-way length, the cross-sectional area of each conductor, and resistivity on a consistent SI basis. The default resistivity is a copper reference near 20°C; connectors, temperature rise, and AC effects are not modeled.

Worked example

For a 12 V, 10 A DC load 5 m one-way from the source on 2.5 mm² copper, Rloop = 2×5×0.01724/2.5 = 0.06896 Ω. The drop is 10×0.06896 = 0.6896 V, about 5.75% of source voltage.

Assumptions and limits

This steady-state estimate uses the entered resistivity for both conductors and a round-trip length of twice the one-way distance. It does not model conductor heating, terminal/contact resistance, transient current, AC effects, voltage-regulation requirements, or allowable ampacity; check wire protection and local electrical requirements separately.

Frequently asked questions

Does cable length mean one-way or round-trip?

Enter the one-way route length. The calculator doubles it for the outgoing and return conductors.

How can I reduce voltage drop?

Shorter runs, larger conductor area, or lower current reduce the resistive drop; check the load’s allowable voltage range.

Does the estimate include connector or fuse losses?

No. Add those resistances separately or measure the installed circuit under load.

How do I use the Two-Wire DC Cable Voltage Drop Calculator?

Enter Source voltage (V), Load current (A), One-way cable length (m), Conductor cross-sectional area (mm²), then complete the remaining labeled fields. Match the units shown beside each field and review the result together with the assumptions below.

What is a worked example of Two-Wire DC Cable Voltage Drop?

For a 12 V, 10 A DC load 5 m one-way from the source on 2.5 mm² copper, Rloop = 2×5×0.01724/2.5 = 0.06896 Ω. The drop is 10×0.06896 = 0.6896 V, about 5.75% of source voltage.