How to use this calculator
Estimate the air volume flow needed to carry a sensible heat load across a chosen temperature difference.
- Enter Sensible heat load, watts, Supply-to-return temperature difference, kelvins, Air density, kg/m³, Air specific heat, J/(kg·K). Match the units shown beside each field and review the result together with the assumptions below.
- Read the worked example below to check the expected input format and result.
- Compare another scenario by changing one input at a time. Use Reset to return to the starting values.
How this calculation works
Air carries sensible heat in proportion to its mass flow, specific heat, and temperature change. This calculator solves the air-side heat balance for volume flow, using the entered air density and specific heat rather than a fixed sea-level shortcut. That makes its assumptions visible and lets users adapt the estimate to their air conditions.
Inputs and units
sensibleLoad— Sensible heat load, watts- Enter sensible heating or cooling load in W; latent load is excluded.
temperatureDifference— Supply-to-return temperature difference, kelvins- Enter the positive temperature change associated with the sensible load.
airDensity— Air density, kg/m³- Use the density for the operating pressure, temperature, and humidity when known.
specificHeat— Air specific heat, J/(kg·K)- Use the specific heat on a mass basis for the air conditions.
Formula
Q_s = ρ cp V̇ ΔT; V̇ = Q_s/(ρ cp ΔT).
Method
Divide the sensible heat load by air density, specific heat, and the supply-to-return temperature difference. Convert the resulting volume flow from m³/s to m³/h and CFM.
Worked example
For a 12,000 W sensible load, 10 K temperature difference, air density 1.204 kg/m³, and specific heat 1,006 J/(kg·K), the required flow is about 0.991 m³/s or 3,567 m³/h.
Assumptions and limits
This is an air-side sensible-heat estimate, not a complete HVAC load calculation. It excludes latent heat, fan heat, duct leakage, and room distribution. Enter density and specific heat for the actual air conditions; standard-air rules of thumb can differ with humidity and elevation.
Frequently asked questions
Is latent cooling included?
No. The relation covers sensible heat from a dry-bulb temperature change only. Moisture removal needs a separate enthalpy or latent-heat calculation.
Why enter air density and specific heat?
The common fixed HVAC factors assume standard air properties. Entered properties make the basis explicit and can improve estimates away from those conditions.
Can I use this airflow as a final duct design?
Treat it as an air-side estimate. A full design also checks loads, duct pressure loss, noise, leakage, balancing, and applicable standards.
How do I use the HVAC Airflow from Sensible Heat Load Calculator?
Enter Sensible heat load, watts, Supply-to-return temperature difference, kelvins, Air density, kg/m³, Air specific heat, J/(kg·K). Match the units shown beside each field and review the result together with the assumptions below.
What is a worked example of HVAC Airflow from Sensible Heat Load?
For a 12,000 W sensible load, 10 K temperature difference, air density 1.204 kg/m³, and specific heat 1,006 J/(kg·K), the required flow is about 0.991 m³/s or 3,567 m³/h.
Reference: ASHRAE Handbook sensible-air heat-balance method. See our calculation methodology.