How to use this calculator
Compare average electrical demand with peak demand over a billing or operating period.
- Enter Energy used (kWh), Peak demand (kW), Period duration (h). Match the units shown beside each field and review the result together with the assumptions below.
- Read the worked example below to check the expected input format and result.
- Compare another scenario by changing one input at a time. Use Reset to return to the starting values.
How this calculation works
Load factor describes how steadily a facility uses power relative to its highest demand. Enter energy over a defined period, the peak demand measured over that same period, and the number of hours in it.
Inputs and units
energy— Energy used (kWh)- Metered energy for the chosen period.
peak— Peak demand (kW)- Maximum billed or measured demand over the same period.
hours— Period duration (h)- Number of hours covered by the energy and peak values.
Formula
Average demand (kW) = energy (kWh) ÷ period hours. Load factor (%) = energy ÷ (peak demand × period hours) × 100.
Worked example
Over 30 days (720 hours), 7,200 kWh averages 10 kW. With a 20 kW peak, load factor is 7,200 ÷ (20 × 720) × 100 = 50%.
Assumptions and limits
Requires positive period hours and peak demand. A result above 100% signals inconsistent units, period boundaries, or demand data; it is not clipped.
Frequently asked questions
Is load factor the same as utilization?
It is a period-based ratio of average to peak demand; utilization may use a different denominator.
What if the value exceeds 100%?
Check the period, demand interval, and units because average demand cannot exceed the measured peak for the same period.
Does it calculate a demand charge?
No. Use the billed peak and tariff rate in a demand-charge calculation for that cost.
How do I use the Electricity load factor calculator?
Enter Energy used (kWh), Peak demand (kW), Period duration (h). Match the units shown beside each field and review the result together with the assumptions below.
What is a worked example of Electricity load factor?
Over 30 days (720 hours), 7,200 kWh averages 10 kW. With a 20 kW peak, load factor is 7,200 ÷ (20 × 720) × 100 = 50%.
Read our calculation methodology.