How to use this calculator
Estimate net positive suction head available at a pump and compare it with the manufacturer’s required NPSH at the intended flow.
- Enter Absolute pressure above liquid surface (kPa), Liquid vapor pressure at operating temperature (kPa), Liquid density (kg/m³), Liquid surface elevation relative to pump inlet (m), then complete the remaining labeled fields. Match the units shown beside each field and review the result together with the assumptions below.
- Read the worked example below to check the expected input format and result.
- Compare another scenario by changing one input at a time. Use Reset to return to the starting values.
How this calculation works
NPSH available is a suction-system property. Convert absolute surface pressure minus vapor pressure into liquid head, add signed static elevation, subtract suction-line losses, then compare the result with the pump curve’s required NPSH.
Inputs and units
surfacePressureKPaAbs— Absolute pressure above liquid surface (kPa)- Use absolute pressure, not gauge pressure; for an open tank this is local atmospheric pressure.
vaporPressureKPaAbs— Liquid vapor pressure at operating temperature (kPa)- Absolute vapor pressure for the pumped liquid at its operating temperature.
densityKgM3— Liquid density (kg/m³)- Density at the operating temperature.
staticHeadM— Liquid surface elevation relative to pump inlet (m)- Positive when the liquid surface is above the pump inlet; negative for suction lift.
suctionLossM— Suction-line head loss (m)- Entered friction and fitting losses from the liquid surface to the pump inlet.
requiredNpshM— Pump required NPSH, NPSHr (m)- Read this value from the selected pump curve at the intended flow.
Formula
NPSHa = 1000·(Psurface,abs − Pvapor,abs)/(ρg) + zstatic − Hloss. NPSH margin = NPSHa − NPSHr, with pressures in kPa, density in kg/m³, and heads in metres.
Method
Use absolute pressure at the free liquid surface and the liquid vapor pressure at operating temperature. Convert their difference to liquid head, add signed surface elevation above the pump inlet, and subtract suction-line loss to estimate NPSHa. Compare with the pump manufacturer’s NPSHr at the same flow.
Worked example
For water with surface pressure 101.325 kPa absolute, vapor pressure 2.34 kPa, density 998.2 kg/m³, a 2 m flooded suction, 1 m suction loss, and NPSHr 3 m, NPSHa is about 11.11 m and the arithmetic margin is about 8.11 m.
Assumptions and limits
This steady-flow estimate assumes negligible velocity at the free surface and that the entered elevation and suction loss refer to the pump inlet. Use absolute pressures, the actual liquid density and vapor pressure at operating temperature, and NPSHr for the intended flow. It does not model transients, entrained gas, or pump-system changes; a positive margin alone is not a guarantee against cavitation.
Frequently asked questions
What is NPSHa?
It is the suction head the system provides above the pumped liquid’s vapor-pressure reference at the pump inlet.
Where do I get NPSHr?
Use the selected pump manufacturer’s curve at the expected flow and operating conditions.
Does a positive margin guarantee no cavitation?
No. The comparison is only a screening check and does not replace the manufacturer’s required margin or a full system review.
How do I use the Pump NPSH Available and Margin Calculator?
Enter Absolute pressure above liquid surface (kPa), Liquid vapor pressure at operating temperature (kPa), Liquid density (kg/m³), Liquid surface elevation relative to pump inlet (m), then complete the remaining labeled fields. Match the units shown beside each field and review the result together with the assumptions below.
What is a worked example of Pump NPSH Available and Margin?
For water with surface pressure 101.325 kPa absolute, vapor pressure 2.34 kPa, density 998.2 kg/m³, a 2 m flooded suction, 1 m suction loss, and NPSHr 3 m, NPSHa is about 11.11 m and the arithmetic margin is about 8.11 m.
Reference: Grundfos technical explanation of pump net positive suction head. See our calculation methodology.